Herunterladen Inhalt Inhalt Diese Seite drucken

Temperature Protection - flamco MeiTronic W10B Bedienungsanleitung

Witterungsgeführte heizungsregler
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

SERVICE SETTINGS FOR ALTERNATIVE ENERGY
SOURCES
Para-
Parameter name
meter
S6.1
MAXIMUM
SOURCE
TEMPERATURE
PROTECTION
MAXIMUM
S6.2
SOURCE
TEMPERATURE
S6.3
SOURCE
SAFETY
SWITCH-OFF
TEMPERATURE
S6.4
SOURCE
FROST
PROTECTION
SOURCE
S6.5
TEMPERATURE
FOR FROST
PROTECTION
OPERATION
S6.6
OF LIQUID
FUEL BOILER
Service setting manual
SERVICE PARAMETERS
Parameter description
With this setting is activated
protection of max. solar collector
or solid fuel boiler temperature.
If solar collector or solid fuel boiler
temprature is exceeded, circulation
pump in solar system will activate
although d. h. w. temperature is
already reached.
Setting of maximum solar collectors
or solid fuel boiler temperature.
If solar collector or solid fuel boiler
emergency shutdown temperature is
exceeded, circulation pump will stop
unconditionally.
If the temperature drops bellow the
set point value (S6.5), the solar pump
switches -on to prevent freezing in
the collectors and pipelines.
NOTE: This setting is suitable only
for climates areas where the
temperature only occasionally
drops bellow the freezing point.
Setting of temperature by which the
collector's frost protection should
activate.
Setting if d. h. w. warming with oil
boiler and solar collectors or solid
fuel boiler can operate at the same
time or oil boiler shall activate with
delay after warming with solar
collectors or solid fuel boiler has
been stopped.
EN
Setting range
Default
setting
0- NO
1
1- YES
90 ÷ 290 °C
120
120 ÷ 350 °C
160
0- NO
0
1- YES
-20 ÷ 10 °C
4
-1- PARALELL
120
0 ÷ 600 MIN-
DELAY OF
LIQUID FUEL
BOILER