flamco MeiTronic W10B Bedienungsanleitung Seite 62

Witterungsgeführte heizungsregler
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

EN
Para-
Parameter name
meter
S7.2
HEAT PUMP
– MAXIMUM
TEMPERATURE
OF THE
SUPPLY
S7.3
HEAT PUMP –
OPERATION
HYSTERESIS
S7.4
HEAT PUMP –
MIN.
OUTDOOR
TEMP. FOR
OPERATION
SWITCH-OFF
HEAT PUMP
S7.5
– OUTDOOR
TEMP. FOR
BIVALENT
OPERATION
MODE
HEAT PUMP
S7.6
– MIN. OUT-
DOOR TEMP.
FOR MONOVA-
LENT OPERA-
TION MODE
62
SERVICE PARAMETERS
Parameter description
Configures the maximum heat
pump operating temperature for
weather-compensated operation.
Configures the heat pump operation
hysteresis.
Configures the limit outdoor
temperature at which the heat
pump operation unconditionally
stops.
Configures the outdoor temperature
for the bivalent operation mode
of the heat pump and the second
energy source. If the temperature is
lower than the configured one, the
controller switches to the second
energy source immediately after the
heat pump can no longer provide the
demanded water temperature. If the
temperature is higher than the con-
figured one, the controller switches
to the second energy source based
on the temperature deficit or with a
delay. This switchover mode enables
maximum use of energy from the
heat pump or use of energy from the
heat pump even if the latter can-
not provide the necessary energy.
entirely.
Configures the minimum outdoor
temperature in the heat pump and
second energy source system. If the
temperature exceeds the minimum
outdoor temperature, heating is per-
formed with a heat pump exclusively.
Setting range
Default
setting
40 ÷ 70 °C
50
2 ÷ 10 °C
3
-30 ÷ 10 °C
-10
11 - NO
STOPPING
-30 ÷ 20 °C
-3
-30 ÷ 20 °C
7
Service setting manual