Herunterladen Inhalt Inhalt Diese Seite drucken

Parameters For Floor Screed Drying - flamco MeiTronic W10B Bedienungsanleitung

Witterungsgeführte heizungsregler
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

PARAMETERS FOR FLOOR
Group F1 contains the parameters for the setting of floor screed drying.
The procedure for F parameters setting is the same as the procedure for
service settings.
TABLE WITH DESCRIPTIONS OF PARAMETRES
Para-
Parameter name
meter
F1.1
FLOOR DRYING FUNCTION ACTIVATION
F1.2
INTERVAL 1: START TEMPERATURE
F1.3
INTERVAL 1: DURATION
F1.4
INTERVAL 2: START TEMPERATURE
INTERVAL 2: DURATION
F1.5
F1.6
INTERVAL 3: START TEMPERATURE
F1.7
INTERVAL 3: DURATION
INTERVAL 4: START TEMPERATURE
F1.8
F1.9
INTERVAL 4: DURATION
F1.10 INTERVAL 4: END TEMPERATURE
FLOOR SCREED DRYING PROFILE - FACTORY SETTING:
Service setting manual
SCREED DRYING
Setting range
0- NO
1- CIRCUIT 1
2- CIRCUIT 2
3- CIRCUIT 1 & 2
10 ÷ 60 °C
1 ÷ 15 days
10 ÷ 60 °C
1 ÷ 15 days
10 ÷ 60 °C
1 ÷ 15 days
10 ÷ 60 °C
1 ÷ 15 days
10 ÷ 60 °C
EN
Default
setting
0
20
10
20
5
45
10
45
5
20
Days
65