Herunterladen Inhalt Inhalt Diese Seite drucken

flamco MeiTronic W10B Bedienungsanleitung Seite 49

Witterungsgeführte heizungsregler
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Para-
Parameter name
meter
S2.4
PUMP OPERA-
TION MODE
S2.5
MINIMUM
STAND-PIPE
TEMPERATURE
MAXIMUM
S2.6
STAND-PIPE
TEMPERATURE
S2.7
STILL STAND
OF MIXING
VALVE
CONTROL
S2.8
MIXING VALVE
P - CONSTANT
S2.9
MIXING VALVE
I - CONSTANT
S2.10 MIXING VALVE
D - CONSTANT
Service setting manual
SERVICE PARAMETERS
Parameter description
Setting of pump operation mode.
Settings have the following meaning:
1- STAND. (circulation pump of
mixing circuit - regular)
2- pump switches off, if requested
room temperature is reached
(only direct circuit)
3- operation according to time
program P1
4- operation according to time
program P2
5- SEL. PROG. (operation according
to selected time program)
Setting of minimum stand-pipe
temperature limitation, when
heating is active.
Setting of maximum stand-pipe
temperature limitation.
Setting of stand-pipe temperature
deviation by which the mixing valve
control is in stand-by.
Setting of mixing valve position
correction intensity. Smaller value
means shorter movements, higher
value means longer mixing valve
movements.
Setting of mixing valve control
frequency - how often mixing valve
position is being controlled. Smaller
value means low frequency, higher
value means higher frequency of
mixing valve corrections.
Sensitivity of mixing valve for
stand-pipe temperature changes.
Smaller value means low sensitivity,
higher value means high sensitivity.
EN
Setting range
Default
setting
1- STANDARD
1
2- SWITCH-
OFF
3- PROG. P1
4- PROG. P2
5- SELECTED
PROGRAM
10 ÷ 90 °C
20
20 ÷ 150 °C
45-
floor
85-
radiat.
0,2 ÷ 3,0 °C
0,6
0,5 ÷ 2,0
1
0,4 ÷ 2,5
1
0,0 ÷ 2,5
1
49