VLT® Compressor Drive CDS 803
操作指南
4.4 压缩机闭环应用启动快速指南
0-01 Language
1
[0]
English
0-06 Grid Type
2
与规格有关
0-60 Main Menu Password
3
[0]
1-13 Compressor Selection
4
与规格有关
1-00 Configuration Mode
5
[0]
Open loop
3-02 Minimum Reference
6
30
Hz
3-03 Maximum Reference
7
200.000
Hz
3-10 Preset Reference
8
[0] 0.00 %
3-15 Reference 1 Source
9
[1]
Analog in 53
3-41 Ramp 1 Ramp Up Time
10
90.00
s
3-42 Ramp 1 Ramp Down Time
11
30.00
s
5
5-12 Terminal 27 Digital Input
12
[2]
Coast inverse
5-40 Function Relay 1
13
[0] [9]
报警
6-19 Terminal 53 mode
14
[1]
电压模式
6-10 Terminal 53 Low Voltage
15
0.07
V
6-11 Terminal 53 High Voltage
16
10.00
V
6-14 Terminal 53 Low Ref./Feedb.
17
与规格有关
6-15 Terminal 53 High Ref./Feedb.
18
Hz
200.000
6-29 erminal 54 mode
19
[0]
0.00
Current mode
6-22 Terminal 54 Low Current
20
4.00
mA
6-23 Terminal 54 High Current
21
20.00
mA
6-24 Terminal 54 Low Ref./Feedb.
22
0.000
0
6-25 Terminal 54 High Ref./Feedb.
23
50.000
20-00 Feedback 1 Source
24
[0]
0.00
No function
20-81 PI Normal/Inverse control
25
[0]
Normal
8-01 Control Site
26
[0]
Digital and ctrl.word
8-30 Protocol
27
[0]
FC
8-32 Baud
28
[2]
9600 Baud
图解 11: 闭环快速指南
表 17: 闭环快速指南
参数
参数 0-01 Language(语言)
参数 0-06 GridType(电网类
型)
60 | Danfoss A/S © | 2019.12
选项
[0] English (英语) [1] Deutsch (德语) [2] Francais
(法语)[3] Dansk(丹麦语)[4] Spanish(西班
牙语)[5] Italiano(意大利语)[28] Bras.port
(巴西葡萄牙语)
[0] 200–240 V/50 Hz/IT-grid[1] 200–240 V/50 Hz/
Delta[2] 200–240 V/50 Hz[10] 380–440 V/50
Hz/IT-grid[11] 380–440 V/50 Hz/Delta[12] 380–
440 V/50 Hz[20] 440–480 V/50 Hz/IT-grid[21]
440–480 V/50 Hz/Delta[22] 440–480 V/50 Hz[30]
525–600 V/50 Hz/IT-grid[31] 525–600 V/50 Hz/
Delta[32] 525–600 V/50 Hz
默认
功能
[0] English(英
选择显示语言
语)
与规格有关
设置变频器在断电后重新连
接电源电压时的运行模式。
AQ32174876762701-000101 / 130R0627
编程