VLT® Compressor Drive CDS 803
Operating Guide
RFI filter
Conduct emission. Maximum shielded cable length [m
type
(ft)]
EN/IEC
Category C3
61800-3
Second environ-
ment Industrial
With-
With
out ex-
exter-
ternal
nal fil-
filter
ter
H4 RFI filter (EN 55011 A1, EN/IEC61800-3 C2)
6.0– 10
kW (8.0–
15 hp)
3x200–
240 V
IP20
H2 RFI filter (EN 55011 A2, EN/IEC 61800-3 C3)
18–30 kW
5 (16.4)
(25– 40
hp)
3x380–
480 V
IP20

6.4 Special Conditions

6.4.1 Derating for Ambient Temperature and Switching Frequency

Ensure that the ambient temperature measured over 24 hours is at least 5 °C (41 °F) lower than the maximum ambient temperature
that is specified for the drive. If the drive is operated at a high ambient temperature, decrease the constant output current. For de-
rating curve, see the VLT® Compressor Drive CDS 803 Design Guide.

6.4.2 Derating for Low Air Pressure and High Altitudes

The cooling capability of air is decreased at low air pressure. For altitudes above 2000 m (6562 ft), contact Danfoss regarding PELV.
Below 1000 m (3281 ft) altitude, derating is not necessary. For altitudes above 1000 m (3281 ft), decrease the ambient temperature
or the maximum output current. Decrease the output by 1% per 100 m (328 ft) altitude above 1000 m (3281 ft) or reduce the maxi-
mum ambient temperature by 1 °C (33.8 °F) per 200 m (656 ft).

6.5 General Technical Data

6.5.1 Protection and Features

Electronic motor thermal protection against overload.
Temperature monitoring of the heat sink ensures that the drive trips if there is overtemperature.
The drive is protected against short circuits between compressor terminals U, V, W.
When a compressor phase is missing, the drive trips and issues an alarm.
When a mains phase is missing, the drive trips or issues a warning (depending on the load).
Monitoring of the DC-link voltage ensures that the drive trips when the DC-link voltage is too low or too high.
The drive is protected against ground faults on compressor terminals U, V, W.
34 | Danfoss A/S © | 2019.12
Housing, trades,
and light indus-
tries
Category C2
Category C1
First environment
First environ-
Home and office
ment Home and
office
With-
With
With-
out ex-
exter-
out ex-
ternal
nal fil-
ternal
filter
ter
filter
25 (82)
50
(164)
Radiated emission
Category C3
Category C2
Second environ-
First environ-
ment Industrial
ment Home and
office
With
With-
With
With-
exter-
out ex-
exter-
out ex-
nal fil-
ternal
nal fil-
ternal
ter
filter
ter
filter
20 (66)
Yes
Yes
No
Specifications
Category C1
First environ-
ment Home and
office
With
With-
With
exter-
out ex-
exter-
nal fil-
ternal
nal fil-
ter
filter
ter
Yes
No
No