VLT® Compressor Drive CDS 803
Operating Guide

3.2.4.5 Recommendation of Fuses

If malfunction occurs, failure to follow the protection recommendation may result in damage to the drive.
Table 11: Fuses
Power [kW (hp)]
3x200–240 V IP20
6.0 (8.0)
7.5 (10)
10 (15)
3x380–480 V IP20
6.0 (8.0)
7.5 (10)
10 (15)
18.5 (25)
22 (30)
30 (40)

3.2.5 EMC-correct Electrical Installation

General points to be observed to ensure EMC-correct electrical installation:
Use only shielded/armored motor cables and shielded/armored control cables.
Ground the shield at both ends.
Avoid installation with twisted shield ends (pigtails), because it reduces the shielding effect at high frequencies. Use the cable
clamps provided.
16 | Danfoss A/S © | 2019.12
N O T I C E
Bussmann
Bussmann
Type RK5
Type RK1
FRS-R-50
KTN-R50
FRS-R-50
KTN-R50
FRS-R-80
KTN-R80
FRS-R-25
KTS-R25
FRS-R-25
KTS-R25
FRS-R-50
KTS-R50
FRS-R-80
KTS-R80
FRS-R-80
KTS-R80
FRS-R-125
KTS-R125
Fuse
UL
Bussmann
Bussmann
Type J
Type T
JKS-50
JJN-50
JKS-50
JJN-50
JKS-80
JJN-80
JKS-25
JJS-25
JKS-25
JJS-25
JKS-50
JJS-50
JKS-80
JJS-80
JKS-80
JJS-80
JKS-R125
JJS-R125
AQ32174876762701-000101 / 130R0627
Installation
Non-UL
Maximum fuse
Type G
50
50
65
25
25
50
63
63
80