3.2.4.5 Recommendation of Fuses
If malfunction occurs, failure to follow the protection recommendation may result in damage to the drive.
Table 11: Fuses
Power [kW (hp)]
3x200–240 V IP20
6.0 (8.0)
7.5 (10)
10 (15)
3x380–480 V IP20
6.0 (8.0)
7.5 (10)
10 (15)
18.5 (25)
22 (30)
30 (40)
3.2.5 EMC-correct Electrical Installation
General points to be observed to ensure EMC-correct electrical installation:
•
Use only shielded/armored motor cables and shielded/armored control cables.
•
Ground the shield at both ends.
•
Avoid installation with twisted shield ends (pigtails), because it reduces the shielding effect at high frequencies. Use the cable
clamps provided.
16 | Danfoss A/S © | 2019.12
N O T I C E
Bussmann
Bussmann
Type RK5
Type RK1
FRS-R-50
KTN-R50
FRS-R-50
KTN-R50
FRS-R-80
KTN-R80
FRS-R-25
KTS-R25
FRS-R-25
KTS-R25
FRS-R-50
KTS-R50
FRS-R-80
KTS-R80
FRS-R-80
KTS-R80
FRS-R-125
KTS-R125
Fuse
UL
Bussmann
Bussmann
Type J
Type T
JKS-50
JJN-50
JKS-50
JJN-50
JKS-80
JJN-80
JKS-25
JJS-25
JKS-25
JJS-25
JKS-50
JJS-50
JKS-80
JJS-80
JKS-80
JJS-80
JKS-R125
JJS-R125
AQ32174876762701-000101 / 130R0627
Installation
Non-UL
Maximum fuse
Type G
50
50
65
25
25
50
63
63
80