VLT® Compressor Drive CDS 803
Operating Guide
Fault
Alarm/
Fault text
num-
warning
ber
bit num-
ber
80
29
Drive initialised
87
47
Auto DC Brak-
ing
95
40
Broken Belt
99
Locked rotor
126
–
Motor Rotating
200
–
Fire Mode
202
–
Fire Mode Lim-
its Exceeded
250
–
New spare part
251
–
New Typecode
Danfoss A/S © 2019.12
Warn-
Alarm
Trip
Cause of problem
ing
lock
–
X
–
All parameter settings are initialized to default settings.
X
–
–
The drive is auto DC braking.
X
X
–
Torque is below the torque level set for no load, indicating
a broken belt. See parameter group 22-6* Broken Belt Detec-
tion.
–
X
–
The rotor is locked or the load is too high.
–
X
–
High back EMF voltage. Stop the rotor of the PM motor.
X
–
–
Fire mode has been activated.
X
–
–
Fire mode has suppressed 1 or more warranty voiding
alarms.
–
X
X
The power or switch mode power supply has been ex-
changed. Contact the local Danfoss supplier.
–
X
X
The drive has a new type code. Contact the local Danfoss
supplier.
Troubleshooting
AQ32174876762701-000101 / 130R0627 | 31