Herunterladen Inhalt Inhalt Diese Seite drucken

Danfoss VLT Compressor Drive CDS 803 Bedienungsanleitung Seite 33

Vorschau ausblenden Andere Handbücher für VLT Compressor Drive CDS 803:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 117
VLT® Compressor Drive CDS 803
Operating Guide
Fault
Alarm/
Fault text
num-
warning
ber
bit num-
ber
80
29
Drive initialised
87
47
Auto DC Brak-
ing
95
40
Broken Belt
99
Locked rotor
126
Motor Rotating
200
Fire Mode
202
Fire Mode Lim-
its Exceeded
250
New spare part
251
New Typecode
Danfoss A/S © 2019.12
Warn-
Alarm
Trip
Cause of problem
ing
lock
X
All parameter settings are initialized to default settings.
X
The drive is auto DC braking.
X
X
Torque is below the torque level set for no load, indicating
a broken belt. See parameter group 22-6* Broken Belt Detec-
tion.
X
The rotor is locked or the load is too high.
X
High back EMF voltage. Stop the rotor of the PM motor.
X
Fire mode has been activated.
X
Fire mode has suppressed 1 or more warranty voiding
alarms.
X
X
The power or switch mode power supply has been ex-
changed. Contact the local Danfoss supplier.
X
X
The drive has a new type code. Contact the local Danfoss
supplier.
Troubleshooting