VLT® Compressor Drive CDS 803
Operating Guide
Table 17: Closed-loop Quick Guide
Parameter
Parameter 0-01 Language
Parameter 0-06 GridType
Parameter 0-06 GridType
Parameter 0-60 Main Menu
Password
Parameter 1-00 Configura-
tion Mode
Parameter 1-13 Compressor
Selection
Parameter 3-02 Minimum
Reference
Parameter 3-03 Maximum
Reference
Parameter 3-10 Preset Refer-
ence
Parameter 3-15 Reference 1
Source
Parameter 3-41 Ramp 1
Ramp Up Time
Parameter 3-42 Ramp 1
Ramp Down Time
Parameter 5-12 Terminal 27
Digital Input
Danfoss A/S © 2019.12
Option
[0] English[1] Deutsch[2] Francais[3]
Dansk[4] Spanish[5] Italiano[28] Bras.port
[0] 200–240 V/50 Hz/IT-grid[1] 200–240
V/50 Hz/Delta[2] 200–240 V/50 Hz[10]
380–440 V/50 Hz/IT-grid[11] 380–440
V/50 Hz/Delta[12] 380–440 V/50 Hz[20]
440–480 V/50 Hz/IT-grid[21] 440–480
V/50 Hz/Delta[22] 440–480 V/50 Hz[30]
525–600 V/50 Hz/IT-grid[31] 525–600
V/50 Hz/Delta[32] 525–600 V/50 Hz
[100] 200–240 V/60 Hz/IT-grid[101] 200–
240 V/60 Hz/Delta[102] 200–240 V/60
Hz[110] 380–440 V/60 Hz/IT-grid[111]
380–440 V/60 Hz/Delta[112] 380–440
V/60 Hz[120] 440–480 V/60 Hz/IT-
grid[121] 440–480 V/60 Hz/Delta[122]
440–480 V/60 Hz[130] 525–600 V/60
Hz/IT-grid[131] 525–600 V/60 Hz/
Delta[132] 525–600 V/60 Hz
0–99
[0] Open loop[3] Closed loop
[24] VZH028-R410A[25] VZH035-
R410A[26] VZH044-R410A[27] VLZ028[28]
VLZ035[29] VLZ044
0–200 Hz
0–200 Hz
-100 to +100%
[0] No function[1] Analog in 53[2] Analog
in 54[7] Pulse input 29[11] Local bus refer-
ence
0.05–3600.0 s
0.05–3600.0 s
[0] No operation[1] Reset[2] Coast in-
verse[3] Coast and reset inverse[4] Quick
stop inverse[5] DC-brake inverse[6] Stop
inverse[7] External Interlock[8] Start[9]
Latched start[10] Reversing[11] Start re-
versing[14] Jog[16] Preset ref bit 0[17] Pre-
set ref bit 1
Default
Function
Select the display language
[0] English
Size related
Select the operating mode for restart
after reconnection of the drive to
mains voltage after power-down.
Size related
Select the operating mode for restart
after reconnection of the drive to
mains voltage after power-down.
0
Define the password for access to the
LCP.
Select closed loop.
[0] Open loop
Size related
Select the compressor used.
30 Hz
The minimum reference is the lowest
value obtainable by summing all refer-
ences.
200 Hz
The maximum reference is the highest
obtainable by summing all references.
0%
Set up a fix setpoint in preset reference
[0].
[1] Analog in
Select the input to be used for the ref-
erence signal.
53
90.00 s
Ramp-up time from 0 to parameter
1-25 Motor Nominal Speed.
30.00 s
Ramp-down time from nominal motor
speed to 0.
Select the input function for terminal
[6] Stop in-
verse
27.
AQ32174876762701-000101 / 130R0627 | 25
Programming