VLT® Compressor Drive CDS 803
Operating Guide
4.5 Changes Made
Changes Made lists all parameters changed from the default settings.
•
The list shows only parameters which have been changed in the current edit setup.
•
Parameters, which have been reset to default values, are not listed.
•
The message Empty indicates that no parameters have been changed.
4.6 Changing Parameter Settings
Procedure
1.
To enter the Quick Menu, press the [Menu] key until the indicator in the display is placed above Quick Menu.
2.
Press [▵] [▿] to select the quick guide, closed-loop setup, compressor setup, or changes made.
3.
Press [OK].
4.
Press [▵] [▿] to browse through the parameters in the Quick Menu.
5.
Press [OK] to select a parameter.
6.
Press [▵] [▿] to change the value of a parameter setting.
7.
Press [OK] to accept the change.
8.
Press either [Back] twice to enter Status, or press [Menu] once to enter the Main Menu.
4.7 Accessing All Parameter via the Main Menu
Procedure
1.
Press [Menu] until the indicator in the display is placed above Main Menu.
2.
Press [▵] [▿] to browse through the parameter groups.
3.
Press [OK] to select a parameter group.
4.
Press [▵] [▿] to browse through the parameters in the specific group.
5.
Press [OK] to select the parameter.
6.
Press [▵] [▿] to set/change the parameter value.
Danfoss A/S © 2019.12
Programming
AQ32174876762701-000101 / 130R0627 | 27