VLT® Compressor Drive CDS 803
Operating Guide
Fault
Alarm/
Fault text
num-
warning
ber
bit num-
ber
44
28
Earth Fault
46
33
Control Voltage
Fault
47
23
24 V supply low
50
AMA calibration
failed
51
15
AMA U
52
AMA low I
53
AMA big motor
54
AMA small mot
55
AMA par. range
56
AMA user inter-
rupt
57
AMA timeout
58
AMA internal
59
25
Current limit
60
44
External Inter-
lock
66
26
Heat sink Tem-
perature Low
69
1
Pwr. Card Temp
70
36
Illegal FC con-
figuration
79
Illegal power
section config-
uration
30 | Danfoss A/S © | 2019.12
Warn-
Alarm
ing
X
X
X
X
X
, I
X
nom
nom
X
nom
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Trip
Cause of problem
lock
X
Discharge from output phases to ground, using the value
of parameter 15-31 Alarm Log Value if possible.
X
Control voltage is low. Contact the local Danfoss supplier.
X
24 V DC supply may be overloaded.
Contact the local Danfoss supplier.
The setting of motor voltage, motor current, and motor
power is wrong. Check the settings.
The motor current is too low. Check the settings.
The motor is too big to perform AMA.
The motor is too small to perform AMA.
The parameter values found from the motor are outside
the acceptable range.
The AMA has been interrupted.
Try to start the AMA again some times, until the AMA is
carried out.
N O T I C E
Repeated runs may heat the motor to a level where the
resistance R
and R
are increased. Usually, however, this
s
r
is not critical.
Contact the local Danfoss supplier.
The current is higher than the value in parameter 4-18 Cur-
rent Limit.
External interlock has been activated. To resume normal
operation, apply 24 V DC to the terminal programmed for
external interlock and reset the drive (via serial communi-
cation, digital I/O, or by pressing [Reset] on the LCP).
This warning is based on the temperature sensor in the
IGBT module (on 400 V, 30 kW (40 hp) and 600 V units).
X
The temperature sensor on the power card exceeds the
upper or lower limits.
X
The control card and power card are not matched.
Internal fault. Contact the local Danfoss supplier.
Troubleshooting
AQ32174876762701-000101 / 130R0627