6.3.3 FMA3 information (sub-menu 10.3)
Access
No.
level
1
1100
FMA3 max. speed
1
1101
FMA3 requested speed
1
1102
FMA3 current speed
1
1103
FMA3 current consumed
1
1104
FMA3 peak supply voltage
1
1105
FMA3 power input
1
1110
FMA3 fault summary
1
1111
FMA3 start-up fault
1
1112
FMA3 rotation direction fault
1
1113
FMA3 current limitation
1
1114
FMA3 temperature limitation
1
1115
FMA3 off
1
1120
FMA3 internal DC voltage
1
1121
FMA3 IGBT temperature
1
1122
FMA3 indoor room temperature
1
1123
FMA3 MCU temperature
1
1124
FMA3 motor temperature
1
1148
FMA3 product code
1
1149
FMA3 software version

7 - FAULT LEVEL (menu 6)

Each type of fault can be forwarded to one of the following two changeover contact relays:
• Non-critical fault relay.
• Critical fault relay.
This menu is used to configure which type of fault will be forwarded to which relay (critical or non-critical).
No.
Description
N02
No air flow (*)
N03
Fan (*)
N05
Filtration fouled
N06
Filtration blocked (*)
N07
Temperature sensors
N08
Electric heater
N09
Humidifier
N11
Water leak
N13
Temperature set high
N14
Temperature set low
N15
Relative humidity set high
N16
Relative humidity set low
Note:
• The faults marked (*) shut down the machine
• If the master/slave function is used, the faults defined as critical stop the unit.
Description
Setting
0: Non-critical fault
1: Critical fault
0: Non-critical fault
1: Critical fault
0: Non-critical fault
1: Critical fault
0: Non-critical fault
1: Critical fault
0: Non-critical fault
1: Critical fault
0: Non-critical fault
1: Critical fault
0: Non-critical fault
1: Critical fault
0: Non-critical fault
1: Critical fault
0: Non-critical fault
1: Critical fault
0: Non-critical fault
1: Critical fault
0: Non-critical fault
1: Critical fault
0: Non-critical fault
1: Critical fault
EN - 21
By default
Display condition
rpm
P05 = 3
rpm
P05 = 3
rpm
P05 = 3
A
P05 = 3
V
P05 = 3
W
P05 = 3
Off/On
P05 = 3
Off/On
P05 = 3
Off/On
P05 = 3
Off/On
P05 = 3
Off/On
P05 = 3
Off/On
P05 = 3
V
P05 = 3
°C
P05 = 3
°C
P05 = 3
°C
P05 = 3
°C
P05 = 3
P05 = 3
P05 = 3
Unit
Display condition
1
1
0
1
1
0
P16 > 0
0
P10 > 0
0
0
P07 > 0 or P08 > 0
0
P07 > 0 or P08 > 0
0
P09 > or P10 > 0
0
P08 > 0 or P10 > 0
EN