Access
No.
Description
level
Control of the duration of release for
3
907
dilution
Cylinder maintenance limit time
(0 = "CY" cylinder life and
3
908
maintenance alarm no longer appears
as a matter of course)
Limit time between two periodic
3
909
releases
3
910
Days of inactivity awaiting release
2
911
Manual drain
2
912
Prewashing
6.2.2 Reading parameters (sub-menu 9.2)
Access
No.
level
1
950
Outdoor request display
1
951
Display of the instantaneous steam flow rate (instantaneous steam)
1
952
Conductivity of supply water
1
953
Current consumed
Maximum production display
1
954
(corresponding to the configured P900 value)
1
955
Nominal steam production
Cylinder hours counter
1
956
(can be reset to 0 by pressing the reset+0 keys for 5 secs)
Machine hours counter
1
957
(cannot be reset to zero; read only)
Humidifier state
0: Not activated
1: Evaporation cycle start
2: Charging with water
3: Evaporating
4: AFS drain
1
958
5: Water drain (for dilution or manual)
6: Water drain ended
7: Complete drain for extended period of inactivity
8: Network or manually requested complete drain
9: Water shortage management
10: Prewash
11: Periodic drain
6.2.3 Alarm (sub-menu 9.3)
Alarm
Mn
EC
E1
E0
EH
EP
EU
EF
ED
To acknowledge a humidifier fault, go into the "ALARM" menu (menu 9.3)
and press the "Reset" key
Setting
50 to 200%
0 h to 4000 h
1 h to 240 h
1 to 199 days
0: without
1: with
0: without
1: with
Description
The humidifier has no fault
Replace the cylinder
Water conductivity too high
Configuration parameter error
Internal memory error
Electrode overcurrent
Low steam flow rate during reduced production
Water level raised without humidification request
Lack of supply water
Drain problem
EN - 19
By default
Display condition
100 %
P10 = 2
3000 h
P10 = 2
24 h
P10 = 2
3 days
P10 = 2
P10 = 2
P10 = 2
Unit
Display condition
%
P10 = 2
kg/h
P10 = 2
µS/cm
P10 = 2
A
P10 = 2
kg/h
P10 = 2
kg/h
P10 = 2
h
P10 = 2
h
P10 = 2
P10 = 2
Description
EN