Herunterladen Inhalt Inhalt Diese Seite drucken

Carrier CCU Controller Bedienungsanleitung Seite 55

Vorschau ausblenden Andere Handbücher für CCU Controller:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Access
No.
level
1
250
Cooling setpoint value
1
251
Temperature setpoint value in heating mode
1
252
Air flow activation threshold value
1
253
Filter fouling activation threshold value
1
254
Filter clogging activation threshold value
1
255
Target temperature
1
256
Target relative humidity
1
257
Filter differential pressure
1
258
Outdoor temperature
1
259
Supply air temperature
1
265
Outdoor humidity
1
266
Raised floor differential pressure
1
268
External weight in water
1
270
Electric heater safety thermostat with manual reset
1
278
External safety contact
1
279
On request contact
1
281
Humidifier maintenance, fault or operation feedback
1
282
Fan operation feedback
1
284
Water leak contact
1
287
Hot water coil or electric heater selection contact
1
288
Summer or winter mode contact
Opening of the heating coil three-way valve or electric heater percentage
1
290
Opening of the heating coil three-way valve
1
291
Opening of the cooling coil three-way valve
1
294
Progressive humidifier percentage
1
295
Fan rotation speed
1
296
Fresh air percentage
1
297
Electric heater percentage
Description
CALCULATED SETPOINT
MEASURED VALUE
LOGIC INPUT STATE (ON/OFF)
PERCENTAGE FOR ANALOGUE OUTPUTS
EN - 17
Unit
Display condition
°C
P07 > 0
°C
P08 > 0
Pa
Pa
Pa
°C
P07 > 0 or P08 > 0
%
P09 > 0 or P10 > 0
Pa
°C
P11 = 1
°C
P06 = 1
P03 = 2 and (P09 > 0 or P10 > 0)
%
and P11 = 1
Pa
P2 = 16
P3 = 2 and (P09 or P10 > 0)
g/Kg
and P11 = 1
default = off
P04 = 0 and (P08 = 1 or (P08 = 2
%
and (P16 = 3 or P16 = 4))
P04 = 1 and (P08 = 1 or P08 = 3)
%
(P07 = 1 or 3) or (P09 = 1 or 3)
%
P10 = 1
%
P02 > 9
%
P11 = 1
P04 = 1 and ((P08 = 2 or P08 =
%
3) and
(P16 = 3 or P16 = 4))
EN

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis