5 - CONFIGURING THE NUMBER OF UNITS

These parameters are only visible if parameter P215 = 1 (master unit)
This sub-menu groups together the operating parameters for the units. They can operate individually or grouped as master/slaves.
Access level
No.
2
C01
Number of units
2
C02
Additional unit
2
C03
Backup unit
2
C04
Additional backup unit
2
C05
Rotation
2
C08
Language used
2
C09
Locking of the configuration
Setpoint for activating the additional
2
C11
unit (authorisation setpoint)
2
C12
Unit rotation time delay
1
C21
Unit rotation counter
Additional unit setpoint
1
C22
(setpoint calculated)
1
C29
Software version number
TREE FOR CONFIGURING THE NUMBER OF UNITS
(only visible if parameter P215 = 1 "master unit")
Description
OPERATING CONFIGURATION
1 to 32: self-contained units
2 to 10: in master/slave
0: No additional unit
1: One additional unit
0: No backup unit
1: One backup unit
0: No additional backup unit
1: One additional backup unit
0: No rotation
(the last unit is the backup unit).
1: Automatic rotation
(according to the time delay adjustable using C12).
0: French
1: English
2: German
3: Spanish
0: Unlocked (the adjusted master/slave functions are
not activated)
1: Locked (the adjusted master/slave functions are
activated).
SETTING
15 to 40°C
(but always 2 K greater than the highest of the P103
cooling setpoints for the units currently operating)
Value adjustable from 0 to 240 h (value '0' is used for
testing and corresponds to a period of 5 minutes)
READ-ONLY
Note: This counter counts down in increments and
when it reaches 0, it is reset to the value for C12 and
the unit whose number precedes the stopped unit or
units stops in turn. The unit whose number precedes
those currently operating starts.
Note: This gives the actual value of the setpoint, i.e. at
least 2 K above the highest cooling setpoint for all units
Setting
EN - 11
By
Display condition
default
1
0
C01 > 1 and C01 < 11
C01 > 1 and C01 < 11
0
and C02 = 1
C01 > 2 and C01 < 11
0
and C02 = 1
0
C02 = 1 or C03 = 1
0
0
27°C
C02 = 1
168 h
C05 = 1
C05 = 1
C02 = 1
EN