Mode Selection - Carrier CCU Controller Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für CCU Controller:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

2
31
Cooling setpoint offset
2
32
Heating setpoint offset
Differential pressure
3
35
measurement
HP/LP pressure
3
36
measurement
Controlled temperature
3
37
sensor type
71
FMA1 configuration (*)
3
72
FMA2 configuration (*)
3
73
FMA3 configuration (*)
3
Locking of the
2
99
configuration
(*) When these parameters are modified, a sequence is launched to configure the FMAs.
6.1.2 CONTROL AND SETTINGS (sub-menu 3.2)
Access
No.
level
1
100
Language used
1
101
Date
1
102
Time
1
103
Temperature setpoint in cooling mode
Temperature proportional band
1
104
in cooling mode
Temperature integral time
1
105
in cooling mode
Temperature setpoint in heating
1
106
mode
Temperature proportional band
1
107
in heating mode
Integral time
1
108
Temperature in heating mode
0: No control
1: Set offset shifted up by outer contact
2: Set offset shifted up by internal timer
0: No shift
1: Set offset shifted down by outer contact
2: Set offset shifted down by internal timer
0: Via 0-10 V pressure sensor
1: Via 0.5 - 4.5 V pressure sensor
0: Via on/off sensors
0: Return sensor fitted
1: Remote room sensor
FMA DIALOGUE CONFIGURATION
0: Not completed
1: Completed
0: Not completed
1: Completed
0: Not completed
1: Completed
0: Configuration unlocked
(The unit cannot be started up; the unit type parameters may be changed).
1: Configuration locked
(The unit can be started up by pressing the "On/Off" push button on
the console. The unit type parameters may no longer be modified. The
number of times the configuration is unlocked is counted.)
Description
0: French
1: English
2: German
3: Spanish
Day/Month/Year
Hours/Minutes
8.0 to 35.0°C if P08 = 0
MAX (15, P106) to 35°C if P08 > 0
1.0 to 10.0 K
0 min 0 s to 30 min 0 s (0 to 1800 s)
10.0 to 35.0°C
10.0 to MIN (35.0, P103)°C
1.0 to 10.0 K
0 min 0 s to 30 min 0 s (0 to 1800 s)
EN - 14

MODE SELECTION

LOCKING
Setting
COOLING CONTROL
HEATING CONTROL
0
P07 > 0
0
P08 > 0
0
0
P17 = at 4
0
P07>0 or P08>0
0
P05 = 1 or 2 or 3
0
P05 = 2 or 3
0
P05 = 3
0
By default
Display condition
0
25.0°C
P07 > 0
2.0 K
P07 > 0
0 min 0 s
P07 > 0
20.0°C
P08 > 0
2.0 K
P08 > 0
0 min 0 s
P08 > 0