6 Commissioning, operation
8) Select the "NEXT" option to display the pressure at which the switch closed and the
hysteresis (DEADBAND).
9) Select the "NEW TEST" option to clear the data and perform another test.
10) Select the "DONE" option to end the test and return to the standard pressure setting.
Example:
[P1] ST will return to [P1].
The previous example uses a normally closed switch. The basic procedure is
effectively the same for a normally open switch, the display will simply read "OPEN"
instead of "CLOSE".
WIKA Operating Instruction, Model CPH65I0
GB
29