7.4.2.11 Switch-off point switching output 1
Switching
Application
2000
This function is used to define the switch-off point of signal output 1 below which the
switching output is deactivated. The left-hand switch point flashes and can be moved using 
(lower) and  (higher) accordingly.
Options: 0 to 100%
The maximum switch-off point is limited to the value of the switch-on point (function 2412),
which means that the switching hysteresis is equal to zero.
7.4.2.12 Switch-on delay switching output 1
Switching
Application
2000
This function can be used to define a switch-on delay for switching output 1. While this delay
is enabled, the measured value must be above the switch-on point (function 2412) for at least
the set time before the switching output is activated.
Options: 100 ms to 20 s, Off
7.4.2.13 Switch-off delay switching output 1
Switching
Application
2000
This function can be used to define a switch-off delay for switching output 1. While this delay
is enabled, the measured value must be below the switch-off point (function 2413) for at least
the set time before the switching output is deactivated.
Options: 100 ms to 20 s, Off
7.4.2.14 Switching function switching output 2
Switching
Application
2000
→ Function 2411
Function group 2420 for switching output 2 is only available for device versions with two
switching outputs.
Endress+Hauser
Switching
outputs
output 1
2400
2410
Switching
outputs
output 1
2400
2410
Switching
outputs
output 1
2400
2410
Switching
outputs
output 2
2400
2420
Switch-off point
output 1
2413
Switch-on delay
output 1
2414
Switch-off delay
output 1
2415
Switching function
output 2
2421
Commissioning
67