7.4.2.3
Current output assignment
Application
Assignment outputs
2000
This function is used to assign the current output to measuring channel 1
(limit, 1M) or measuring channel 2 (motion, 2M).
Options: "Limit (1M)", "Motion (2M)"
7.4.2.4
Current output mode
Application
Current output
2000
This function can be used to switch on output magnify.
4 mA
Standard
Grenzstand 1
4 mA
Function 2320
30 Current output mode
For this function, a small segment of the 0 to 100 % detection range is shown on the current
output of 4 to 20 mA.
Options: "Standard", "Magnify"
7.4.2.5
4mA value of the magnify
Application
Current output
2000
This function is used to enter the percentage value for the lower limit (4 mA) while the
magnify is enabled (function 2310).
Options: 0 to 100 %
7.4.2.6
20mA value of the magnify
Application
Current output
2000
This function is used to enter the percentage value for the upper limit (20 mA) while the
magnify is enabled (function 2310).
Options: 0 to 100%
The 4mA value (function 2310) must always be lower than the 20mA value; if it is not,
an error message is displayed.
Endress+Hauser
2200
2300
20 mA
082
%
Magnify
20 mA
Function 2330
2300
2300
Current output
2230
Current output mode
2310
4mA value
2320
20mA value
2330
Commissioning
65