Nivotester FTR525
7.4.1
Adjustments to the application
The Soliwave FQR57/FDR57 microwave barrier must be adjusted to suit the application for
commissioning; the following functions of the application main function group (2000) can be
used for this.
7.4.1.1
Automatic setup of level limit detection
Application
Sensor
2000
Automatic setup is carried out with either a free or a covered path;
the option selected for this corresponds to the state of the path.
Options: "Free path", "Covered path"
The following manual adjustment functions can be used to carry out fine adjustment of the
microwave barrier or to suit changing application conditions.
7.4.1.2
Manual adjustment lower limit (LL) level limit detection
Application
Sensor
2000
This function can be used to change the lower limit of the set detection range using  (for
reducing the set detection range 0 to 100 %) or  (for increasing the set detection range 0 to
100 %). To assist with adjustment, the current measured value is shown alongside the
set detection range.
Example
Current measured value within the
set detection range
2 1 1 2
1M
4
3
Max. detection range
Set detection range
27 Manual adjustment lower limit (LL) level limit detection display with examples
1
Percentage value for the lower limit relative to the maximum possible detection range
2
Current measured value
3
Set detection range (= 0-100% of signal output)
4
Lower limit (adjustable using this function)
Endress+Hauser
Limit detection
2100
2110
Limit detection
2100
2110
018
Automatic setup
2111
Manual adjustment LL
2112
Current measured value at the limit
of the set detection range
1
2
Current measured value outside of
the set detection range
Commissioning
000
000
065
61