3.3

Close mounting

If several devices are mounted on a switch board above or next to each other, the panel cut-
outs must be positioned 35 mm horizontally and at least 80 mm vertically away from each oth-
er.
3.4

Insertion in panel cut-out

Step
1
2
3
4
3.5

Care and treatment of the front cover

The front plate can be cleaned with commercial detergents and cleaning agents.
Activity
Affix delivered panel seal (1) on the device from the rear
Insert the device into the panel cut-out from the front and ensure the panel seal is correctly
positioned so that no water or dirt can penetrate the case.
From the panel rear, slide the mounting brackets into the guides on the sides of the case. In
doing so, the flat faces of the mounting brackets must make contact with the case.
Place the mounting brackets against the panel rear and tighten evenly with a screwdriver
until the controller housing is firmly positioned in the panel cut-out.