Hang the unit into the top rail.
Slide the locking clip upwards again, so that the unit is
retained to the bottom rail. The unit is now fixed in place.
3 3
Plug the AC and data connectors into the inverter (right
hand side).
If there is only one inverter, the AC/data connectors are
not required.
If a StecaGrid Control N or StecaGrid Control D resp. D1
control unit is not used, the AC/data connectors in the
last unit are also not required.
4 4
Position the next inverter on the rail and connect it to
the first one.
5 5
Repeat steps  to 4 until the system reaches the desired
size (max. of 3,600 Watts AC power).
6 6
When using the StecaGrid Control N or StecaGrid Control
D resp. D1control unit connect the control unit to the last
inverter (see chapter 4.. 'Installation of the Control Unit').
WARNING!
Risk of death by electrocution!
Do not touch bare cable ends.
Disconnect cables from the solar module before cutting
them to size.
7 7
Connect the cables from the solar panels (DC cables) to
the inverter plugs.
Make sure the + / - wires are connected to the plugs
correctly (male/female) and correctly coded. The ne-
gative connection terminal on the inverter is always
closest to the wall.
If there is an adequate supply of sunlight, the inver-
ters will switch to the 'Stand-by' mode: this is indica-
ted when the LED flashes.
As the mains supply has not yet been connected, the
inverter will not generate an output voltage.
WARNING!
Risk of death by electrocution!
The unit may only be connected to the grid by qualified
personnel in accordance with the regulations of the local
power supply company.
44
717.545 | 08.13