Installation and Connection
3.5

Control Board Compact/General

3.5.1 X2A Control Terminal Strip

1 2 3 4 5 6 7 8 9
• Tightening torque 0,22...0,25 Nm (2 lb inches)
• Use shielded/drilled cables
• Lay shield on one side of the inverter onto earth potential
PIN Function
1
+ Set value input
2
- Set value input
3
+ Analog input
4
- Analog input
Progr. analog outputs
5
Analog output 1
6
Analog output 2
7
+ 10 V Output
8
Analog Mass
9
Analog Mass
Prog. Digital inputs
10 Fixed frequency 1 (CP.19) I1
11 Fixed frequency 2 (CP.20) I2
12 External fault
13 DC-braking
14 Forw ard
15 Reverse
16 Control release/ Reset
17 Reset
Digital outputs
18 Transistor output 1
19 Transistor output 2
20 24 V-Output
21 20...30 V-Input
22 Digital Mass
23 Digital Mass
24 Relay 1 / NO contact
25 Relay 1 / NC contact
26 Relay 1 / sw itching contact RLC
27 Relay 2 / NO contact
28 Relay 2 / NC contact
29 Relay 2 / sw itching contact FLC
46
10 11 12 13 14 15 16 17 18 19 20 21 22 23
Name Description
AN1+ Differential voltage inputs 0...±10 VDC; Ri = 55kOhm
AN1- AN1: Setting of the analog set value
AN2+ AN2: no function at KEB factory settings
AN2-
0...±10 VDC / max. 5 mA; defined by the manufacturer
AO1
Output of the actual output frequency 0...±100 Hz
AO2
Output of the apparent current 0...2 x I
CRF
Reference voltage for set value poti (max. 4 mA)
COM Mass for analog in- and outputs
COM Mass for analog in- and outputs
Function of the inputs is defined by the manufacturer
13...30 VDC ±0% smoothed; Ri: 2,1 kOhm; scan time 1 ms
I1 + I2 = Fixed frequency 3 (CP.21)
I3
Input for external fault setting (E.EF)
I4
Activates the DC-braking (CP.22/23)
F
Preset rotation;
R
Forw ard has priority
ST
Pow er modules are enabled; reset at opening
RST
Reset; only w hen an error occurs
max. 50 mA; function is defined by the manufacturer
O1
sw itched at factual = fset
O2
Ready signal (sw itched as long as no error occurs)
U
Supply of the programmable inputs
out
U
Voltage input for external supply
in
0V
Potential for digital in- /outputs
0V
Potential for digital in- /outputs
RLA
Programmable relay output (CP.31)
RLB
Load ability max. 30 VDC / 0.01...1A
Factory setting: Fault relay
FLA
Programmable relay output (CP.32)
FLB
Load ability max. 30 VDC / 0.01...1A
Factory setting: Frequency dependent sw itch