Herunterladen Inhalt Inhalt Diese Seite drucken

Connection Of Power Circuit; Terminal Strip X1A; Wiring Instructions - KEB COMBIVERT F5 Installationsanleitung

B-gehäuse
Vorschau ausblenden Andere Handbücher für COMBIVERT F5:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Installation and Connection
3.3

Connection of Power Circuit

3.3.1 Terminal Strip X1A

Terminal strip X1A/ 230 V class suitable for
• 180...260 V AC / 1-phase (L1/N)
• 180...260 V AC / 3-phase (L1, L2, L3)
• DC-Supply 250...370 V DC (++, --)
• ++, PB
• U, V, W
• T1, T2

3.3.2 Wiring instructions

Absolutely observe the connecting voltage of the KEB COMBIVERT.
A 230V-unit will be immediately destructed on a 400V-power supply.
Never exchange the mains and motor cables.
Some countries demand that the PE-terminal is directly connected
to the terminal box (not over the mounting plate).
40
Terminal strip X1A/ 400 V class suitable for
• 305...500 V AC / 3-phase (L1, L2, L3)
• DC-Supply 420...720 V DC (++, --)
Braking resistor
Motor
Temperature sensor / switch (see chapter 3.3.6)