Installation and Connection

3.3.4 Motor connection

• max. motor line length see chapter 2.3
Motor-PTC
(optionally)

3.3.5 Connection of the temperature monitoring

Terminals T1, T2
Tripping resistance 1.65...4 kOhm
Reset resistance 0.75...1.65 kOhm
Design in accordance with VDE 0660 Part 302
This function can be activated by the machine builder by software
Do not lay connecting cable together with control cable
Permissible in the motor cable only with double shielding
Connect relay K1 for fire prevention in regenerative operation (see 3.3.6)
K1
12
42
M
3~
PE
U
V
W
Other
11
Apply shieldings over a large
contact surface of the
mounting plate
Motor-PTC
X1A
L1
N/L2
L3
++
--
PB
U
V
W
T1
T2
T1
T2