Connection of the supply unit
PE
L1
L2
L3
3.2.2
Connection of a braking resistor
Connection of the Power Unit
Mains Connection of the Supply Unit
• absolutely use a line reactor
• if the dimensioning is not 1:1 --> insert fuses
• in case of interconnected operation with several supply units
consider information sheet 00.R5.0DM-I000 !
L1
L1
L2
L2
L3
L3
L1
L2
L3
R5
-
Connection of the Braking Resistor
It is absolutely necessary to monitor the braking resistance temperature switch
to record a braking resistance overheat. The overheat may be caused by:
• incorrect dimensioning of the braking resistance
• the input voltage being too high
The current of the brake transistor is monitored additionally. The input thyristors
are switched off in case of a short circuit.
Braking resistors can develop a very high surface temperatures, therefore install
as safe-to-touch as possible!
As standard the evaluation at
terminals T1 and T2 is switched off
and must be activated if necessary
(application mode Pn.12="7").
Installation
PE
T1 T2
T1 T2
PE
DC-FU
+
+ +
U
T1 T2
PE
DC-FU
V W
+ +
U
V W
M
M
~
3
3
PA
PA
PB
PB
OH1
T1
OH2
T2
GB - 35
~