Herunterladen Inhalt Inhalt Diese Seite drucken

Assignment Of The Terminal Block X2B; Inputs; 2.5.1.1 Specification Of The Sto Inputs; 2.5.1.2 Sto With Ossd Signals - KEB COMBIVERT F5 Installationsanleitung

Steuerteil mit sicherheitsfunktion "sto"
Vorschau ausblenden Andere Handbücher für COMBIVERT F5:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Control
2.5

Assignment of the terminal block X2B

2
4
1
3 5
The individual channels are designed potential-free, so 24V and 0 V can be connected. The
inputs are designed by way that safety switchgear units with test pulses (OSSD signals) can
be connected. The signals are not evaluated, they are only filtered. The OSSD test interval
is limited to 10 ms.
The output STO-OUT at terminal 9/10 is switched against the mass of the control.
2.5.1

inputs

2.5.1.1 Specification of the STO inputs
STO
inputs
max.
min.
The maximum short-term starting current of the input is limited to 300 mA.
2.5.1.2 STO with OSSD signals
The filter time depends on the minimum input voltage and can be specified as follows:
2.5.2

Output STO

The short-circuit proof, digital output is specified in accordance with IEC61131-2. The output
rated current is 100 mA at 24 Vdc. The output is active, if the inputs STO1 and STO2 are set.
GB - 16
X2B
PIN
6
8
10
7
9
10
Status 0
UL [V]
5
-3
Input voltage [V]
15
18
20
24
30
Name
1
STO1+
2
STO1+
3
STO1-
4
STO1-
5
STO2+
6
STO2+
7
STO2-
8
STO2-
9
STO-OUT
STO-OUT
IL [mA]
25
not defined
I/O
Input STO channel 1
Input STO channel 2
Output STO
Status 1
UH [V]
30
15
OSSD pulse width [ms]
0.1
0.8
1.1
1.5
1.8
IH [mA]
25
5

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis