Configuring the software
•
Location: Name of the room that is conditioned by this unit
•
Area: Area to which this unit belongs.
IU Type: Model of the indoor unit that was recognised by the
•
system
IU Model: Exact model of the indoor unit.
•
•
OU Type: Model of the outdoor unit that was recognised by
the system. (3*)
•
OU Model: Exact model of the outdoor unit.
•
OU is FX: Indicates that the outdoor unit is a 3-pipe unit (3*)
•
OU is R410A: Indicates that the refrigerant is R410A (3*)
Serial OU: Serial number of the outdoor unit (3*)
•
•
Serial IU: Serial number of the indoor unit.
•
RCS Group: Number of the Remote Controller that is used by
more than one indoor unit, incluiding this one (1*)
•
CH Box: Number of the CH distribution Box used by more
than one indoor unit, including this one.(2*)
Unit configuration for water chillers:
Location: name assigned to the water chiller, for example re-
•
ferring to the area in which it operates or its primary function.
IU type: the type of unit detected by the system
•
•
Chiller model: the exact model to be entered by the user
•
Chiller serial: the series number to be introduced by the user
•
Low temperature mode: the low-temperature mode may be:
None, Type 1, Type 2 or Type 3. This is the mode indicated
in the catalog for the chiller and which enables it to access a
lower range of temperatures in cooling mode. In these mo-
des, and following the indications in the technical catalog for
the chiller, additives must be used in order to prevent the pro-
cessed water from freezing.
•
Energy meter address: the address ModBus (from 1 to 32)
of the power meter connected to the chiller. 0 (zero) or blank
indicates that there is no power meter connected.
17
PMML0164A rev.2 - 10/2012
•
RCS Control: Sets the RCS Control as master, slave or RCS
not installed.
•
Sec. Address: in set free of H-LINK (I) with more than 16
indoor units, we use a virtual address to indicate that this unit
is a secondary unit of the previously unit.
•
Cool Range: value range of the temperature in cooling mode.
•
Heat Range: value range of the temperature in heating mode.
N O T E
• If the RCS is used by only one IU, this number is not required.
• If the CH is used by only one IU, this number is not required.
• All of the data related to the OU is shown directly to the other
IU in the same refrigerant circuit.
Click 'Update' to update the data.
Water flow: flow rate of water processed in the water chiller.
•
This should be entered in m³/h.
Specific heat: value of the specific heat resulting from the
•
mixture of water with the antifreeze additive. This should be
entered in joules • kg-1 • K-1.
•
Glychol percent: percentage of anti-freeze added to water.
Glychol density: density of anti-freeze added to water.
•
•
Master address: set this chiller as a master of the existing in
the H-LINK line.
N O T E
The power meter parameters require the additional configuration
of the power meter explained in the technical catalogue