MONTAGE-, BEDIENUNGS- UND WARTUNGSANLEITUNG
CAD-COMPACT ADVANCED
Modbus
Register
address
description
152
Minimum voltage processed
by AIN1
153
Maximum voltage processed
by AIN1
154
K factor for exhaust air fan
Notes:
* the value range of these parameters depends on set value: Minimum and maximum fan control
** minimum value of this parameter depends on the value set as the lowest control set point (parameter 88)
Modbus
Register description
address
200
Supply temperature sensor
defective
201
Extraction temperature sensor
defective
202
External temperature sensor
defective
203
Exhaust temperature sensor
defective
204
-
205
-
206
Defective Internal ΔP1 sensor
207
Defective internal ΔP2 sensor
208
Contamination of supply air filter
or exhaust air filter
209
General inspection required on
manufacturer service
210
No confirmation of fans correct
operation
211
Possible overheating of pre-hea-
ter
212
Possible overheating of
post-heater
213
Overheating of pre-heater –
triple thermostat activation
214
Overheating of post-heater –
triple thermostat activations
215
Anti-freeze procedure activation
for pre-heater
216
Anti-freeze procedure activation
for post-heater
217
Too high supply temperature –
protection procedure turned ON
218
Too low supply temperature –
protection procedure turned ON
Seite 56
Value
Min.
Max.
Def.
0
10
0
0
10
10
0
1000
84
Value
Min.
Max.
Def.
0
1
0
0
1
0
0
1
0
0
1
0
-
-
-
-
-
-
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
CAD COMPACT ADVANCED
Register
Variable
Notes
options
type
R/W
integer
Unit: V
R/W
integer
Unit: V
R/W
float
Einstellungen resolution: 0.1; to modify the
parameter please send: requested value x 10
Register
Variable
Notes
options
type
R
integer
0 – alarm inactive;
1 – alarm active
R
integer
0 – alarm inactive;
1 – alarm active
R
integer
0 – alarm inactive;
1 – alarm active
R
integer
0 – alarm inactive;
1 – alarm active
R
-
-
R
-
-
-
integer
0 – alarm inactive;
1 – alarm active
-
integer
0 – alarm inactive;
1 – alarm active
R
integer
0 – alarm inactive;
1 – alarm active
R
integer
0 – alarm inactive;
1 – alarm active
R
integer
0 – alarm inactive;
1 – alarm active
R
Integer
0 – alarm inactive;
1 – alarm active
R
Integer
0 – alarm inactive;
1 – alarm active
R
Integer
0 – alarm inactive;
1 – alarm active
R
Integer
0 – alarm inactive;
1 – alarm active
R
Integer
0 – alarm inactive;
1 – alarm active
R
Integer
0 – alarm inactive;
1 – alarm active
R
Integer
0 – alarm inactive;
1 – alarm active
R
Integer
0 – alarm inactive;
1 – alarm active
DEUTSCH

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis