Herunterladen Inhalt Inhalt Diese Seite drucken

S&P CAD COMPACT ADVANCED 900 Bedienungsanleitung Seite 51

Wrg-flachgerät mit regelung
Vorschau ausblenden Andere Handbücher für CAD COMPACT ADVANCED 900:
Inhaltsverzeichnis

Werbung

MONTAGE-, BEDIENUNGS- UND WARTUNGSANLEITUNG
CAD-COMPACT ADVANCED
Modbus
Register
address
description
6
UID - chars 9 and 10
7
UID - chars 11 and 12
8
UID - chars 13 and 14
9
UID - chars 15 and 16
10
UID - chars 17 and 18
11
UID - chars 19 and 20
12
Correct work status of the unit
(supply or exhaust fans should
be on)
13
Unit alarm state
14
Minute to be set in internal
clock
15
Hour to be set in internal clock 0
16
Day of month to be set in eco-
VENT internal clock
17
Month to be set in internal
clock
18
Year to be set in internal clock
19
Regulation set on main tempe-
rature sensor
20
Set temperature for regulation
21
Supply air temperature
22
Extraction air temperature
23
Exhausted air temperature
24
Outdoor air temperature
25
-
26
-
27
-
28
Main sensor number
29
State of digital inputs
30
Signal from pre-heater ther-
mostat
31
Signal form post-heater ther-
mostat
32
Signal from therm3ostats (i. e.
for two electrical heaters)
33
Signal from burglar alarm
system
34
Signal from Fire Alarm System
(FAS)
35
Signal from relative humidity
switch
36
Signal from CO2 switch
37
Remote deactivation signal
38
Boost activation signal
DEUTSCH
Value
Min.
Max.
Def.
12336
23130
-
12336
23130
-
12336
23130
-
12336
23130
-
12336
23130
-
12336
23130
-
0
1
1
0
1
0
0
59
1
23
1
1
31
1
1
12
1
15
99
20
-40
85
0
8
30
0
-40
85
0
-40
85
0
-40
85
0
-40
85
0
-
-
-
-
-
-
-
-
-
2
3
3
0
31
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
0
1
0
CAD COMPACT ADVANCED
Register
Variable
Notes
options
type
R
ASCII
-
R
ASCII
-
R
ASCII
-
R
ASCII
-
R
ASCII
-
R
ASCII
-
R
integer
0 – unit (fans) stops ;
1 – unit (fans) works
R
integer
0 – inactive;
1 – active
R/W
integer
R/W
integer
R/W
integer
R/W
integer
R/W
integer
Only two last digits were set
R
integer
999 – if sensor were damaged;
Unit: °C
R/W
integer
Unit: °C
R
integer
999 – if sensor were damaged;
Unit: °C
R
integer
999 – if sensor were damaged;
Unit: °C
R
integer
999 – if sensor were damaged;
Unit: °C
R
integer
999 – if sensor were damaged;
Unit: °C
-
-
-
-
-
-
-
-
-
R/W
integer
2 – supply sensor;
3 – extraction sensor
R
HEX
0x01 – DIN1 shorten;
0x02 – DIN2 shorten;
0x04 – DIN3 shorten;
0x08 – DIN4 shorten;
0x10 – DIN5 shorten
R
integer
0 – no signal;
1 – signal is active
R
integer
0 – no signal;
1 – signal is active
R
integer
0 – no signal;
1 – signal is active
R
integer
0 – no signal;
1 – signal is active
R
integer
0 – no signal;
1 – signal is active
R
integer
0 – no signal;
1 – signal is active
R
integer
0 – no signal;
1 – signal is active
R
integer
0 – no signal;
1 – signal is active
R
Integer
0 – no signal;
1 – signal is active
Seite 51