Herunterladen Inhalt Inhalt Diese Seite drucken

S&P CAD COMPACT ADVANCED 900 Bedienungsanleitung Seite 53

Wrg-flachgerät mit regelung
Vorschau ausblenden Andere Handbücher für CAD COMPACT ADVANCED 900:
Inhaltsverzeichnis

Werbung

MONTAGE-, BEDIENUNGS- UND WARTUNGSANLEITUNG
CAD-COMPACT ADVANCED
Modbus
Register
address
description
74
Set regulation mode
75
Set operating mode
76
Current season mode (Summer
/ Winter mode)
77
Temperature with winter mode
being turned ON
78
Hysteresis with summer mode
being turned ON
79
Anti-freezing mode state
80
Pre-set supply air fan control in
VAV 1 mode
81
Pre-set exhaust air fan control
in VAV 1 mode
82
Pre-set supply air fan control in
VAV 2 mode
83
Pre-set exhaust air fan control
in VAV 2 mode
84
Pre-set supply air fan control in
VAV 3 mode
85
Pre-set exhaust air fan control
in VAV 3 mode
86
Minimum voltage to start linear
characteristic control by CO2 in
AUTO-VAV mode
87
Maximum voltage end linear
characteristic control by CO2 in
AUTO-VAV mode
88
Pre-set SAF and EAF control at
start of linear characteristic in
AUTO-VAV mode
89
Pre-set SAF and EAF control at
the end of linear characteristic
in AUTO-VAV mode
90
Exhaust fan control shift in
AUTO-VAV mode
91
Pre-set airflow - supply air in
CAV 1 mode
92
Pre-set airflow - exhaust air in
CAV 1 mode
93
Pre-set airflow - supply air in
CAV 2 mode
94
Pre-set airflow - exhaust air in
CAV 2 mode
95
Pre-set airflow - supply air in
CAV 3 mode
DEUTSCH
Value
Min.
Max.
Def.
1
4
0
0
15
0
0
4
4
-20
20
6
0
20
14
0
1
0
Dyn.*
Dyn.*
100
Dyn.*
Dyn.*
100
Dyn.*
Dyn.*
60
Dyn.*
Dyn.*
60
Dyn.*
Dyn.*
30
Dyn.*
Dyn.*
30
0.0
10.0
2.0
0.0
10.0
8.0
2
10
4.5
Dyn.**
10
10
-50
50
0
0
4000
3000
0
4000
3000
0
4000
2000
0
4000
2000
0
4000
1000
CAD COMPACT ADVANCED
Register
Variable
Notes
options
type
R/W
integer
0x01 – VAV mode;
0x02 – CAV mode;
0x04 – COP mode
R/W
integer
0 – OFF mode;
2 – manual control;
3 – mode 1;
4 – mode 2;
5 – mode 3;
8 – mode AUTO VAV;
9 – mode AUTO CAV;
10 – mode AUTO COP;
12 – mode timer VAV;
13 – mode timer CAV;
14 – mode timer COP
R/W
integer
0x01 – Summer mode;
0x02 – Winter mode;
0x04 – Auto mode
R/W
integer
Unit: °C
R/W
integer
Unit: °C
R
integer
0 – anti-freezing mode inactive;
1 – anti-freezing mode active
R/W
integer
Unit: %
R/W
integer
Unit: %
R/W
integer
Unit: %
R/W
integer
Unit: %
R/W
integer
Unit: %
R/W
integer
Unit: %
R/W
float
Einstellungen resolution: 0.1; to modify the
parameter please send: requested value x 10
R/W
float
Einstellungen resolution: 0.1; to modify the
parameter please send: requested value x 10
R/W
float
Einstellungen resolution: 0.1; to modify the
parameter please send: requested value x 10
R/W
float
Einstellungen resolution: 0.1; to modify the
parameter please send: requested value x 10
R/W
integer
Unit: %
R/W
integer
Unit: m3/h
R/W
integer
Unit: m3/h
R/W
integer
Unit: m3/h
R/W
integer
Unit: m3/h
R/W
integer
Unit: m3/h
Seite 53