Description Of Request/Response Data Items - Balluff BNI CCL-502-100-Z001 Betriebsanleitung

Cc-link io-link master
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
6
Acyclic messaging
6.4. Description of
request/response
data items
www.balluff.com
Item
Access code
Selects the access area
For request message: (Control)
Control
0x02 = Write
(Status)
0x03 = Read
Index /
Index
Port Number
Port Number = IO-Link Channel number
Identification data of the gateway, for details refer to the section "5.3 IO-Link
overview", table "Description of the gateway identification data"
Index
0x00-0x0A
0x10
Identification
0x11
data
0x12
0x13
0x14
0x15
0x16
0x17
The process data size setting for each IO-Link channel can be read and written. The
value shows the mapped process data size for each IO-Link channel in Words (0 -
16). The sum of all IO-Link channel's data size + message transmission area must
not exceed the maximum available Word area, which is determined by the number of
occupied stations and extended cyclic setting. See also CC-Link Profile Number.
The order in which IO-Link process and parameter data is mapped can be set
with bit 7 (high byte/ low byte).
Process data
size
b7
ISDU
Reading / Writing IO-Link parameter data
The event data (Event qualifier and event code) of a pending event indicated
Event data
by the IO-Link channel event flag can be read. After reading the event data the IO-
Link port event flag changes to 0.
IO-Link device validation. The validation type is defined as follows:
0x00 = validation deactivated
0x01 = validation of IO-Link Vendor ID and IO-Link Device ID
Validation
0x02 = validation of IO-Link Vendor ID, IO-Link Device ID and serial number
data
Depending on the configuration of the IO-Link device validation, the connected
device's information is verified and the result indicated by the port LED 'IO-link' and
'IO-Link Channel established' flag.
Description
= Address of the gateway identification data (details in the next row)
Object Name
Not used
Vendor name
Vendor text
Product name
Product code
Product text
Not used
Hardware Revision
Firmware Revision
b4
b3
b2
b1
b0
For response message: (Status)
0x00
= OK
0x01 – 0xFF = Error (see details in 6.4)
Type
N/A
Read
Only
Process data size (valid: 0-16)
Refer to section "7.1 Profile Presets"
High byte / low byte swapping
for IO-Link process- and parameter data
0: swapping enabled
1: swapping disabled
19