Description
89
Slave alarm offline
90
Alarm from master
91
Evaporator defrost
timeout alarm
92
Evaporator 2
defrost timeout
alarm
93
Sequential defrost
skipped on slave 1
alarm
94
Sequential defrost
skipped on slave 2
alarm
95
Sequential defrost
skipped on slave 3
alarm
96
Sequential defrost
skipped on slave 4
alarm
Instruction manual
v. 00 | 9600-0033
Rev.
BEST W R290
Cause
Probable incorrect
Slave unit in alarm
connection or
state not
disconnection of
considered by the
the master/slave
master in the
line
master/slave
functions
Serious alarm in
The master unit is
progress in master
blocked, the slave
unit
devices work
independently with
their own
parameters
Evaporator defrost
Visual indication
ended due to
only
maximum time and
not due to
temperature
Evaporator defrost
Visual indication
ended due to
only
maximum time and
not due to
temperature
Defrost cycle
Defrost not
skipped on slave 1
performed, only
during the
visual indication
sequential defrost
stage due to
missing conditions
for longer than dT1
+ tdc + dt + 1
minute (parameters
of the master)
Defrost cycle
Defrost not
skipped on slave 2
performed, only
during the
visual indication
sequential defrost
stage due to
missing conditions
for longer than dT1
+ tdc + dt + 1
minute (parameters
of the master)
Defrost cycle
Defrost not
skipped on slave 3
performed, only
during the
visual indication
sequential defrost
stage due to
missing conditions
for longer than dT1
+ tdc + dt + 1
minute (parameters
of the master)
Defrost cycle
Defrost not
skipped on slave 4
performed, only
during the
visual indication
sequential defrost
stage due to
missing conditions
for longer than dT1
+ tdc + dt + 1
minute (parameters
of the master)
© 2020 RIVACOLD srl
 | 
Impact
Resolution
Check the
connection of the
master/slave line or
the parameters of
the NET unit
Check the master
unit and check the
alarm in progress
Check the defrost
end value dT1 or the
maximum duration
value dS1
Check the defrost
end value dT2 or the
maximum duration
value dS2
Check the
conditions of the
unit and if
necessary, check
parameter dT1
Check the
conditions of the
unit and if
necessary, check
parameter dT1
Check the
conditions of the
unit and if
necessary, check
parameter dT1
Check the
conditions of the
unit and if
necessary, check
parameter dT1
EN
8.  Diagnostics
Reset
Relay
(*)
A
No
A
No
A
No
A
No
A
No
A
No
A
No
A
No
141