8.  Diagnostics
ID
Description
56
General gas leak
alarm
57
Regulation
temperature probe
alarm
58
Regulation suction
pressure probe
alarm
59
Regulation
condensing
pressure probe
alarm
60
Evaporator fan
regulation probe
alarm
61
Evaporator 2 fan
regulation probe
alarm
62
Regulation low
suction pressure
alarm
63
Regulation
condensing high
pressure alarm
64
Regulation
condensing low
pressure alarm
65
Safety defrost
probe alarm
66
General alarm probe
1 alarm
138
BEST W R290
Cause
Probable refrigerant
Stopped machine
leak in the unit
circuitry or
evaporator blocked
with ice
Probe(s) used for
Stopped machine,
regulation in alarm
emergency cycle
state
starts if activated
Probe(s) used for
Visual indication
regulation in alarm
only, if the Leak
state
function or
parameter A63=1 is
enabled, the
machine is stopped
Probe(s) used for
Condenser fans
regulation in alarm
forcing at 100%.
state
Visual indication
only, if parameter
A67=1 and A71=1
the machine is
stopped
Probe(s) used for
Visual indication
regulation in alarm
only, evaporator
state
fans run
continuously
Probe(s) used for
Visual indication
regulation in alarm
only, evaporator 2
state
fans run
continuously
Suction Pressure
If parameter A63=1
below the threshold
the machine is
set in parameter
stopped, otherwise,
A65
visual indication
only
Condensing
Condenser fans
pressure above the
forcing at 100%. If
threshold set in
parameter A67=1
parameter A69
the machine is
stopped, otherwise,
visual indication
only
Condensing
If parameter A71=1
pressure below the
the machine is
threshold set in
stopped, otherwise,
parameter A73
visual indication
only
Probe(s) used for
Deactivation of the
the safety defrost
safety defrost
function in alarm
function
state
Probe(s) used for
Deactivation of the
the generic function
generic function
in alarm state
Impact
Resolution
Check the circuitry
and whether there is
a leak or check the
condition of the
evaporator,
probably blocked
with ice
Check probe alarms
and verify their state
and connections
Check probe alarms
and verify their state
and connections
Check probe alarms
and verify their state
and connections
Check probe alarms
and verify their state
and connections
Check probe alarms
and verify their state
and connections
Check whether the
pressure in the
circuit is consistent
with that measured
and if necessary,
modify tripping
threshold A65
Check whether the
pressure in the
circuit is consistent
with that measured
and if necessary,
modify tripping
threshold A69
Check whether the
pressure in the
circuit is consistent
with that measured
and if necessary,
modify tripping
threshold A73
Check probe alarms
and verify their state
and connections
Check probe alarms
and verify their state
and connections
Instruction manual
v. 00 | 9600-0033
Rev.
Reset
Relay
(*)
M
Yes
A
Yes
A
Yes
A
Yes
A
No
A
No
A
Yes
A
Yes
A
No
A
No
A
No