5. Installation
5.2 Setting the packaged unit in place
5.2.1 Characteristics of the placement area
NOTICE: The packaged unit must only be installed inside rooms that fully shelter it.
The placement area must have the following characteristics:
The place of installation must have good air circulation and must be far from heat sources (e.g. naked
l
flames or hot surfaces) and from electrical components or flammable materials
the wall must be vertical with an adequate surface to support the weight of the packaged unit, even, well
l
leveled and free from vibrations
the walls of the coldrooms must not be thicker than 200 mm. A 100 mm plug-in insulating panel is
l
supplied as standard for NT units, whereas the standard plug-in insulating panel is 150 mm for LT units.
the place of installation must have a temperature indicated in "Technical features" on page 146.
l
5.2.2 Minimum distances of the placement area
The packaged unit must be positioned in a placement area with minimum distances to allow proper air
circulation and facilitate maintenance.
5.2.3 Removing the packaging
NOTICE: Environmental contamination. Follow the regulations in force regarding the disposal of polluting materials.
Remove all packaging and fastening elements used during transport.
5.2.4 Inspections and checks on the packaged unit
Visually inspect the packaged unit to look for any damage caused during transport that could compromise
normal operation. Transport damage must be attributed to the carrier and immediately reported to
RIVACOLD srl.
5.2.5 Storage
If the packaged unit must be stored for long periods, for example waiting to be relocated, follow the
instructions below.
Isolate the packaged unit from energy sources.
l
Clean the packaged unit and all its components.
l
100
BEST W R290
Instruction manual
Rev.
v. 00 | 9600-0033