7.  Maintenance
7.1.4 Maintenance on equipment components
Perform maintenance by following the instructions, frequencies and all indications in the manuals and in the
attached documentation. If necessary, contact RIVACOLD srl assistance.

7.2 Maintenance and cleaning performed by the operators

7.2.1 Required skills
Operator
7.2.2 Safety
DANGER!
Explosion/Burn. Presence of flammable gas. During maintenance, adopt all the
precautions required by legislation in force and the warnings for adjustments and maintenance
indicated in this instruction manual.
CAUTION! Low temperatures. During maintenance and cleaning in the coldroom, take breaks to avoid
long exposure to low temperatures.
Only perform the maintenance and cleaning described in this instruction manual and observe the indicated
maintenance frequency.

7.2.3 Daily operations

Task
Check
Cleaning

7.2.4 Weekly operations

Task
Defrost
120
Always wear helmets, footwear and protective gloves.
Component
Packaged unit
Check that the packaged unit is in good condition.
Clean as needed.
Evaporating part
and condensing
unit
Component
If there is ice on the evaporating part:
Evaporator
1. Perform the manual defrost cycle (see "Control
2. Repeat the procedure until completely defrosted.
3. Check again after 12 hours
BEST W R290
Procedure
Procedure
panel operations" on page 112).
Instruction manual
v. 00 | 9600-0033
© 2020 RIVACOLD srl
Rev.
 | 
Indicative
time
[min]
5
30
Indicative
time
[min]
-