Parameter Value
1..255
P-4
1|0-65535
2|0-65535
3|0-65535
4|0-65535
5|0-65535
6|0-65535
7
8
11
12
13
14
15|0-65535
16|0-65535
17
20
21
22|0-65535
23|0-65535|0-65535 Function code read/write multiple registers, read address range 0 - 65535,
24|0-65535
40
42
43
48
66
67
90
100
125
126
0..255
P-5
none
yes
P-6
no
yes
P-7
no
yes
P-8
no
1 1 .1 .3
dpi m odbus m odifyprofile
Modifies a profile in the DPI MODBUS profile table.
Mode: Global Config Mode
Privilege Level: Operator
Format: dpi modbus modifyprofile <P-1> [description <P-2>] [function-type <P-3>]
[function-code-list <P-4>] [unit-identifier-list <P-5>] [sanity-check <P-6>]
[exception <P-7>] [reset <P-8>]
[description]: Profile description/name for the DPI MODBUS profile.
[function-type]: Function type of corresponding function codes.
[function-code-list]: Function code list. A function code has the syntax 'val'. Function codes are separated
by a comma. When more than one value for an function code is specified the values are separated by the pipe
symbol ('|').
[unit-identifier-list]: Unit identifier list. A unit identifier has the syntax 'val'. To specify no options, the
value 'none' must be given. Unit identifiers are separated by a comma.
[sanity-check]: Sanity check including format and specification.
[exception]: Device exception message.
[reset]: Reset connection message.
Parameter Value
1..32
P-1
string
P-2
RM CLI EAGLE40-07
Release 04.1.01 05/2021
Meaning
Function codes 1 - 255
Function code read coils, coil address range 0 - 65535
Function code read discrete inputs, input address range 0 - 65535
Function code read holding registers, register address range 0 - 65535
Function code read input registers, register address range 0 - 65535
Function code write single coil, coil address range 0 - 65535
Function code write single register, register address range 0 - 65535
Function code read exception status
Function code diagnostic
Function code get com event counter
Function code get comm event log
Function code program (584/984)
Function code poll (584/984)
Function code write multiple coils, coil address range 0 - 65535
Function code write multiple registers, register address range 0 - 65535
Function code report slave id
Function code read file record
Function code write file record
Function code mask write register, register address range 0 - 65535
write address range 0 - 65535
Function code read fifo queue, pointer address range 0 - 65535
Function code program (concept)
Function code concept symbol table
Function code encapsulated interface transport
Function code advantech co. ltd. - management functions
Function code scan data inc. - expanded read holding registers
Function code scan data inc. - expanded write holding registers
Function code unity programming/ofs
Function code scattered register read
Function code schneider electric - firmware replacement
Function code schneider electric - program
Unit identifier 0 - 255
No unit identifier 'none'
True
False
True
False
True
False
Meaning
Profile index 1 - 32
Profile description/name
47