17Dpi Iec104 Modify - Belden HIRSCHMANN EAGLE40-07 Referenzhandbuch

Grafische benutzeroberfläche; anwender-handbuch konfiguration
Vorschau ausblenden Andere Handbücher für HIRSCHMANN EAGLE40-07:

Werbung

Parameter Value
112
113
120
121
122
123
124
125
126
127
128..135
..
1..2
P-5
0..255
P-6
0..255
0..255
0..255
0..255/65535
P-7
0..255/65535
0..255/65535
0..255/65535
enable
P-8
disable
enable
P-9
disable
enable
P-10
disable
1..2
P-11
1..3
P-12
enable
P-13
disable
1 1 .1 .1 7 dpi ie c 1 0 4 m odify
Modifies a profile in the DPI IEC104 profile table.
Mode: Global Config Mode
Privilege Level: Operator
Format: dpi iec104 modify <P-1> [description <P-2>] [function-type <P-3>] [adv-type-
id-list <P-4>] [transmission-size <P-5>] [originator-addr-list <P-6>] [common-
addr-list <P-7>] [sanity-check <P-8>] [reset <P-9>] [debug <P-10>] [common-addr-
size <P-11>] [io-addr-size <P-12>] [allow-101 <P-13>]
[description]: Description/name for the DPI IEC104 profile.
[function-type]: Function type.
[adv-type-id-list]: Advanced type ID list.
[transmission-size]: Set cause of transmission size.
[originator-addr-list]: Originator address list (Configurable when cause of transmission size is 2).
[common-addr-list]: Common address list (For common address size 1, range is 0-255 and for common
address size 2, range is 0-65535).
[sanity-check]: Sanity check including format and specification.
[reset]: Reset connection message.
[debug]: Debug output in reset message.
[common-addr-size]: Set Common Address Size.
[io-addr-size]: Set IO address size.
[allow-101]: Allow IEC101 type IDs.
Parameter Value
1..32
P-1
string
P-2
readonly
P-3
readwrite
common
any
advanced
52
Meaning
Parameter of measured value, short floating point value p-me-nc-1
Parameter activation p-ac-na-1
File ready f-fr-na-1
Section ready f-sr-na-1
Call directory, select file, call file, call section f-sc-na-1
Last section, last segment f-ls-na-1
Ack file, Ack section f-af-na-1
Segment f-sg-na-1
f-dr-ta-1
QueryLog - Request archive file f-sc-nb-1
Reserved for routing of messages
Type ID from 136-255 and undefined type IDs are reserved for special use
Specify the cause-of-transmission size.
Set originator address.
Set list of originator address with comma seperated e.g 1,5.
Set range of originator address e.g 5-10.
Set list and range of originator address e.g 1,5-10,120-255.
Set common address.
Set list of common address with comma seperated e.g 1,5.
Set range of common address e.g 5-10.
Set list and range of common address e.g 1,5-10,120-300.
Enable the option.
Disable the option.
Enable the option.
Disable the option.
Enable the option.
Disable the option.
Specify the common address size.
Specify the IO address size.
Enable the option.
Disable the option.
Meaning
Profile index 1 - 32
Profile description/name
Read only type IDs for type ID list.
Read write type IDs for type ID list.
Common type IDs for type ID list.
All possible type IDs for type ID list (allow any type ID).
Lets the user specify customized type IDs for type ID list.
RM CLI EAGLE40-07
Release 04.1.01 05/2021