Parameter Value
string
P-2
readonly
P-3
readwrite
common
any
advanced
1..255
P-4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
30
31
32
33
34
35
36
37
38
39
40
45
46
47
48
49
50
51
58
59
60
61
62
63
64
70
100
101
102
103
104
105
106
107
110
111
RM CLI EAGLE40-07
Release 04.1.01 05/2021
Meaning
Profile description/name
Read only type IDs for type ID list.
Read write type IDs for type ID list.
Common type IDs for type ID list.
All possible type IDs for type ID list (allow any type ID).
Lets the user specify customized type IDs for type ID list.
Comma separated type ID e.g 1,2,3.
Single point information m-sp-na-1
Single point information with time tag m-sp-ta-1
Double point information m-dp-na-1
Double point information with time tag m-dp-ta-1
Step position information m-st-na-1
Step position information with time tag m-st-ta-1
Bit string of 32 bit m-bo-na-1
Bit string of 32 bit with time tag m-bo-ta-1
Measured value, normalized value m-me-na-1
Measured value, normalized value with time tag m-me-ta-1
Measured value, scaled value m-me-nb-1
Measured value, scaled value with time tag m-me-tb-1
Measured value, short floating point value m-me-nc-1
Measured value, short floating point value with time tag m-me-tc-1
Integrated totals m-it-na-1
Integrated totals with time tag m-it-ta-1
Event of protection equipment with time tag m-ep-ta-1
Packed start events of protection equipment with time tag m-ep-tb-1
Packed output circuit information of protection equipment with time tag m-ep-
tc-1
Packed single-point information with status change detection m-ps-na-1
Measured value, normalized value without quality descriptor m-me-nd-1
Single point information with time tag cp56time2a m-sp-tb-1
Double point information with time tag cp56time2a m-dp-tb-1
Step position information with time tag cp56time2a m-st-tb-1
Bit string of 32 bit with time tag cp56time2a m-bo-tb-1
Measured value, normalized value with time tag cp56time2a m-me-td-1
Measured value, scaled value with time tag cp56time2a m-me-te-1
Measured value, short floating point value with time tag cp56time2a m-me-tf-1
Integrated totals with time tag cp56time2a m-it-tb-1
Event of protection equipment with time tag cp56time2a m-ep-td-1
Packed start events of protection equipment with time tag cp56time2a m-ep-te-1
Packed output circuit information of protection equipment with time tag
cp56time2a m-ep-tf-1
Single command c-sc-na-1
Double command c-dc-na-1
Regulating step command c-rc-na-1
Setpoint command, normalized value c-se-na-1
Setpoint command, scaled value c-se-nb-1
Setpoint command, short floating point value c-se-nc-1
Bit string 32 bit c-bo-na-1
Single command with time tag cp56time2a c-sc-ta-1
Double command with time tag cp56time2a c-dc-ta-1
Regulating step command with time tag cp56time2a c-rc-ta-1
Setpoint command, normalized value with time tag cp56time2a c-se-ta-1
Setpoint command, scaled value with time tag cp56time2a c-se-tb-1
Setpoint command, short floating point value with time tag cp56time2a c-se-tc-1
Bit string 32 bit with time tag cp56time2a c-bo-ta-1
End of initialization m-ei-na-1
(General-) Interrogation command c-ic-na-1
Counter interrogation command c-ci-na-1
Read command c-rd-na-1
Clock synchronization command c-cs-na-1
( IEC 101 ) Test command c-ts-nb-1
Reset process command c-rp-nc-1
( IEC 101 ) Delay acquisition command c-cd-na-1
Test command with time tag cp56time2a c-ts-ta-1
Parameter of measured value, normalized value p-me-na-1
Parameter of measured value, scaled value p-me-nb-1
51