Continue to Pump
Protection Setup?
Sleep Mode
Minimum/Sleep Speed
Sleep Delay
Wake-up Speed
Continue to the Pump Protection menu to set the remaining pump protection options, or press the Back but-
ton to exit the Genie.
3.3.5 Feedback Setup
Follow steps from 1 to 3 and then proceed as follows.
Setup Selection
Control Feedback Sources
Feedback 1 Source
Analog Input 53
Low Feedback 1 Value
High Feedback 1 Value
10,00 [Unit]
Yes
Enable
20.0 Hz
1 s
30.0 Hz
Feedback
1
0,0 [Unit]
6. Select YES for pump protection setup.
7. Select Enable to let the pump stop below Mini-
mum/Sleep Speed value.
8. Select the Minimum/Sleep speed frequency value.
Below this value the pump will stop.
9. Select the Sleep Delay value in seconds.
10. Select the Wake-up Speed. Above this value the
pump will start.
1. Select Feedback Setup
2. Select number of feedbacks of your system (1 if
you have only one sensor for each inverter)
3. Select the analog input where the sensor is con-
nected
4. Set minimum of sensor scale
5. Set Sensor Full Scale
en - Original instructions