• Install the circuit breaker where it can be easily accessed by the
agent.
• When installing the circuit breaker outdoors, install one which is
designed to be used outdoors.
• Under no circumstances the power wire must not be extended.
Connection trouble in the places where the wire is extended may
give rise to smoking and/or a fire.
• Electrical wiring work shall be conducted according to law and
regulation in the community and installation manual. Failure to do
so may result in electrocution or short circuit.
Test run
• Before operating the air conditioner after having completed the
work, check that the electrical control box cover of the indoor
unit and service panel of the outdoor unit are closed, and set the
circuit breaker to the ON position. You may receive an electric
shock if the power is turned on without first conducting these
checks.
• If there is any kind of trouble (such as an error display has
appeared, smell of burning, abnormal sounds, the air conditioner
fails to cool or heat or water is leaking) has occurred in the air
conditioner, do not touch the air conditioner yourself but set
the circuit breaker to the OFF position, and contact a qualified
service person (*1). Take steps to ensure that the power will not
be turned on (by marking "out of service" near the circuit breaker,
for instance) until qualified service person (*1) arrives. Continuing
to use the air conditioner in the trouble status may cause
mechanical problems to escalate or result in electric shocks or
other trouble.
11-EN
• After the work has finished, use an insulation tester set
(500V Megger) to check the resistance is 1 MΩ or more between
the charge section and the non-charge metal section (Earth
section). If the resistance value is low, a disaster such as a leak
or electric shock is caused at user's side.
• Upon completion of the installation work, check for refrigerant
leaks and check the insulation resistance and water drainage.
Then conduct a test run to check that the air conditioner is
operating properly.
Explanations given to user
• Upon completion of the installation work, tell the user where the
circuit breaker is located. If the user does not know where the
circuit breaker is, he or she will not be able to turn it off in the
event that trouble has occurred in the air conditioner.
• If the fan grille is damaged, do not approach the outdoor unit but
set the circuit breaker to the OFF position, and contact a qualified
service person (*1) to have the repairs done. Do not set the
circuit breaker to the ON position until the repairs are completed.
• After the installation work, follow the Owner's Manual to explain
to the customer how to use and maintain the unit.