6.9 Menu SERVICE
This menu item is provided for the Bender service personnel and is protected
by a password against erroneous settings. It is intended to provide fast fault
clearance by qualified experts in the event of a device error.
6.10 Parameterization via Internet
The parameters of an IRDH275B indicated below can be checked and set from
a remote place of use by using a personal computer. In addition, a browser
(viewing program for Internet application) and the BMS-Ethernet-Gateway
COM465 are required.
Remote setting is possible for:
•
Response value Alarm 1 (1 kΩ...10 MΩ)
•
Response value Alarm 2 (1 kΩ...10 MΩ)
•
Operating principle alarm relay 1 (e.g. N/O operation)
•
Operating principle alarm relay 2 (e.g. N/O operation)
•
Measuring principle (AMP or DC)
•
Current output ranges for external measuring instruments
(0/4...20 mA)
•
Maximum system leakage capacitance (150 μF or 500 μF)
•
Time for repetition of the automatic self test (off/ 1 h/ 24 h
•
Starting time of the automatic self test (0.00...23.00 h)
•
Language of the alarm messages to be displayed (D, GB)
•
Setting the fault memory to ON or OFF
64
Operation and setting
IRDH275_D00122_03_M_XXEN/05.2017