8. Fault finding the product

WARNING
Electric shock
Death or serious personal injury
Switch off the power supply before you start any work
on the product.
Make sure that the power supply cannot be switched
on accidentally.
Fault finding and fault correction must be carried out by qualified
persons.

8.1 Overview of alarm and warning codes

Code number
Code 2
Code 4
Code 9
Code 12
Code 22
Code 25
Code 48
Code 57
Code 69
Code 84
Code 117
Code 157
Code 159
Code 165
20
1
Description
The power phase is missing.
Too many motor restarts.
The power-phase sequence is
wrong.
Service is needed.
Moisture in motor of pump.
Wrong configuration.
The motor is overloaded.
Missing water in the application.
The winding temperature is too
high.
The memory-storage media is
faulty.
The door is opened.
Real-time clock monitoring.
Communication error, CIM xxx.
Signal fault.
Code number
Code 181
Code 191
Code 205
Code 225
Code 226
Code 229

8.2 Code 2 (Power phase missing)

Alarm code 2 is shown on the display.
The alarm symbol on the display turns red and the pump stops.
Alarm code Power phase missing is displayed in Grundfos
GO Remote.
Cause
The product is configured for 2 or 3 phases but only 1 phase is
connected.
Remedy
Make sure that the Mains Power connection setting is
correct according to the number of phases connected (1, 2 or
3 phases).
Cause
One of the power supply phases is not connected.
Remedy
Connect the phase.
Cause
The fuse is blown somewhere on the incoming power line.
Remedy
Replace the fuse.
Related information
2.3.3 Connecting the pump supply and power supply

8.3 Code 4 (Too many motor restarts)

Alarm code 4 is shown on the display.
The alarm symbol on the display turns red and the pump
stops.
Alarm code Too many motor restarts is displayed in Grundfos
GO Remote.
Cause
The pump has been blocked or partly blocked causing overload in
the motor.
Remedy
Remove the blockage from the pump.
Related information
6.14 Setting the maximum number of restarts with Grundfos GO
Remote

8.4 Code 9 (Power phase sequence wrong)

Alarm code 9 is shown on the display.
The alarm symbol on the display turns red and the pump
stops.
Alarm code Power phase sequence wrong is displayed in
Grundfos GO Remote.
Cause
The power supply phase is set incorrectly.
Remedy
Interchange two phases.
Description
Signal fault, PTC input.
High water level.
Level-switch inconsistency.
Communication error, pump
module.
Communication error, IO
module.
Water on the floor.