10. Overview of inputs and outputs

DI:
Digital input
DO: Digital output
AO: Analog output
AI:
Analog input
NC: Normally closed contact
NO: Normally open contact
C:
Common
Position numbers, see fig. 2.
Pos.
Terminal
Designation
Connection of phase
L
conductor
Connection of neutral
1
N
conductor
Connection to
PE
protective earth
A1
RS-485 A
Y1
RS-485 GND
2
B1
RS-485 B
Functional earth
A
RS-485 A
Y
RS-485 GND*
B
RS-485 B
3**
Functional earth
10
DI 1
11
GND
12
DI 2
13
GND
4
14
DI 3
All terminals (except mains terminals) must only be connected to voltages
not exceeding 16 V
Ethernet RJ45
5
External computing devices connected to the Ethernet connection must
comply with the standards IEC 60950 and UL 60950.
6
GENIbus
50
+24 V
51
AI 1
53
+24 V
7
54
AI 2
57
AI 3
58
GND
All terminals (except mains terminals) must only be connected to voltages
not exceeding 16 V
Data
1 x 100-240 VAC ± 10 %, 50/60 Hz
GENIbus (internal)
(Fix the screen with a cable clamp.)
External GENIbus (not standard)
(Fix the screen with a cable clamp.)
Digital input
and 22.6 V
or 35 VDC.
rms
peak
Service connection
Supply to sensor. Maximum 30 mA
Input for analog signal,
0/4-20 mA or 0-10 V
Supply to sensor. Maximum 30 mA
Input for analog signal,
0/4-20 mA or 0-10 V
and 22.6 V
or 35 VDC.
rms
peak
Diagram
CU 351
L
L
N
N
PE
CU 351
IO 351
A1
A
Y1
Y
B1
B
CU 351
A
Y
B
10
11
12
13
14
50
1
51
53
2
54
3
57
58
13