Configuring interfaces
Open: Device Menu > Configuration > Ethernet
Configuration item Selection/settings
Assign IP address
Manual IP address
Subnet mask
Standard gateway
DNS server
Transfer rate
a
To enter an IP configuration manually, a valid available IP address on the network must
be known. Contact your network administrator to obtain the parameters for manual IP
configuration.
NOTICE!
In the Versatronic, the TCP port 502 is set permanently to Modbus/TCP
and cannot be changed.
With Modbus/TCP, it is not necessary to configure the Modbus device
address. Bus users are identified by their IP addresses. The Unit ID
(Modbus device address in the Modbus/TCP telegram) is set permanently
to 255 in the Versatronic (
Each host on a network must have a unique IP address. If an IP address
exists several times on the network, an address conflict will result. It must
be ensured that fixed IP addresses lie outside the DHCP IP address range
and are assigned only once.
The transmission times in an Ethernet network depend on the network
structure and the traffic, among other things. As a result, delays in updating
the process values may occur when using Modbus/TCP.
417102397 Rev. 1-10.2019
Description
Manually: If no DHCP server is installed on the network
and the IP address configuration is known (e.g. by the
network administrator), the data are entered manually.
Manually
Automatically: A DHCP server is installed on the network.
Automatically
After being switched on and booted the Versatronic
receives the IP configuration from the DHCP server; IP
configuration takes place automatically.
IP address of the device to use for Modbus/TCP (Modbus
Valid IP address
a
communication via Ethernet)
The subnet mask specifies which part of the IP address
functions as the network address and which part as the
a
Valid subnet mask
host address. It can be used to create subnetworks on a
network.
IP address of the standard gateway
The standard gateway is required for routing into other
a
Valid IP address
networks. Without the standard gateway, the Versatronic
can communicate only with hosts in its own subnetwork.
IP address of the DNS server
DNS = Domain Name System
This service permits the DNS name resolution. This is
a
Valid IP address
necessary if the Versatronic is to be accessed by entering
a URL in a web browser. Without DNS, the IP address
must be entered in the web browser.
Automatic
Transmission speed (bit rate) and duplex mode of the
10 Mbit/s half duplex
Ethernet optional board
10 Mbit/s full duplex
This setting must match the setting of the switch or router
100 Mbit/s half duplex
ports to which the Versatronic is connected.
100 Mbit/s full duplex
Ä Chapter 7.1 'Modbus/TCP' on page 39).