1-2 => M
ENCODER
1 -> S
2 -> +
3 -> GND
The length of connection cables from the motors to the control panel unit must not exceed 15 m.
The wire section of the motor power supply must be 1.5 mm
As for the encorder it is very important to use a shielded wire with a section of 0,75 mm
It is compulsory to use shielded cable for the encoder in order to guarantee the correct operation of the control board.
The shield of the ENCODER cable must be earth grounded at one end (not to the card GND), and at the opposite end the shield must be
free (conductor not connected).
To ensure the correct functioning of the installation it is advisable to wire encoder and motor with separate cables.

ELECTRIC CONNECTIONS

WARNING!
2
, whilst that of the accessories must be 0,75 mm
PRINCE
Where:
=> WHITE-RED-BLUE are the plugs of the connector
where you have to insert the 3 WIRES (NOT THE
SHIELD !)
=> S, +, GND are the plugs of the control board where
you have to insert the 3 WIRES. The SHIELD must be
connected to the EARTH from the power supply (not to
GND).
2
.
2
type ÖLFLEX-110 CH.