ER10-20-35-45-60-100 Electrical schemes

REP. DESIGNATION
FCO Open limit switch
FCF Closed limit switch
FC1 Auxiliary 1 limit switch
FC2 Auxiliary2 limit switch
M
Motor
T
Thermal fuse
D
Led
C
Capacitor
* For all other voltages, contact Valpes Sales department.
DSBA1619GB rev.26/07/04
The operation of electrical appliance can appear dangerous because it implies the
powering of certain components.
Any intervention on installation or electric components must be carried out by
specialized electricians or qualified people under the direction and the monitoring
of electricians to follow the rules in force.
- It's necessary to remove the cover to connect the strips.
- Pull out the handle or the half ball indicator.
- Free the screws of the cover with a screwdriver, remove it.
- Free the gland and insert the feeding cable into the housing and connect as follows:
Our ISO20 glandless can fit 5,5 to 12mm cables. (option 1/2 '' NPT threaded)
1. POWER AND REMOTE CONNECTING
- Realize the connection as followed :
ALTERNATING CURRENT 24V-115V- 230V AC
- Connect the earth on faston
- Connect neutral in 1
- Connect the wire of open in 2
- Connecter the wire of close in 3 ( phase in 50/60hz alternatively on 2 & 3)
DIRECT CURRENT 12V-24V DC
- Connect 1 and 2 du double inverseur ou relais (REP.A) nécessaire au fonctionnement en
courant continu.
- Make a shunt (REP. B) between 2 & 3.
- Reverse the connections, if Opening & Closing are not in the right position.
2. AUXILIARY LIMIT SWITCHES SETTING
As standard, these actuators are provided with 2 auxiliary limit switches adjusted for the rotation
requested.
Caution : connect wiring in respect of the electrical standards, auxiliary limit switches
are powered by a very low voltage (<42V *).
Cover off, procide as before, free the second gland' screw and connect the wiring as follows:
- connect 4 and 8 for the switch FC1, 6 and 9 for the switch FC2 = normaly closed or
- connect 4 and 5 for the switch FC1, 6 and 7 for the switch FC2 = normaly open NO
VALPES goods offers the possibility of a finest adjustment according to the detailed method
see page 19 "Auxiliary limit switches setting".
- Tighten the gland. Put the cover and tighten the screws of the cover.
- Put back the handle or the indicator on the shaft.
115V—230V AC
12V—24V AC/DC
GB
21