5
Technical Information
Use
In any configuration menu it is possible to come back at the upper menu,
NOTE
without storing any modifications, by pressing the MODE key.
Selecting the options AWG 6 or AWG 8, the unit shows:
S
Press ▲ or ▼ to set the pump cable length from 3 to 50 m, then press
SET to confirm the choice.
Selecting the option CUSTOM, the unit shows:
S
Press ▲ or ▼ to set the total pump cable Electrical Resistance at
20°C (Rcable) from 12 to 250 mΩ;
Where:
then press SET to confirm the choice.
If the pump cable Electrical Resistance is more than 200 mΩ, the controller
NOTE
doesn't assure the full current (50A) to the load all over the range of supply
voltage.
The display shows:
C
Press▲ or▼ to select the Source Type option:
C
88/127
E
L
E
C
T
E
L
E
C
T
R
= single wire per-unit-length resistance [mΩ/m] @20°C
PUL
L
= pump cable length [m]
c
O
N
F
I
G
S
E
L
E
O
N
F
I
G
S
O
U
R
L
E
N
3
m
R
E
S
1
2
m
R
= 2 * R
* L
cable
PUL
c
:
C
T
C
:
C
E
T
TSP Controller User Manual / 87-900-138-01