KB36/1 - AUTONOMY EXPANSION KIT (optional)
This kit allows the autonomy of the UPS to be increased by adding 1 or more sets of 3 batteries
to the UPS (single cabinet version).
KB36/2 - AUTONOMY EXPANSION KIT FOR DOUBLE CABINET (optional)
This kit allows the autonomy of the UPS to be increased by adding 1 or more sets of 3 batteries
to the UPS (double cabinet version).
OUT/2 (optional)
This accessory enables parallel connection of additional battery units to the standard battery unit
supplied, to increase the autonomy of the UPS.
BAT 36 (optional)
An additional battery unit complete with battery connection cables which can house from 1 to 10
AUTONOMY EXPANSION KITS. One or more BAT 36 units can be connected in parallel to the
standard battery unit by means of one or more OUT 2.
PW 1000 (optional)
This kit makes it possible to increase the power of the UPS by adding one or more power
modules inside the unit, up to a maximum of four in the single cabinet version and eight in the
double cabinet version (supplied without additional batteries).
SPECIAL FUNCTIONS SET UP
To set special functions, when the UPS is switched-off, press the SERVICE button [11] on the
rear panel of the UPS. The UPS will beep and the LEDs on the front panel will show the status
of the following options:
- MAINS LED [3] on
- BATTERY LED [4] on
- BYPASS LED [7] on
- INVERTER LED [8] on
- OVERLOAD LED [6] on
- PROTECTION LED [5] on
To select the desired function press the Buzzer Off button [2] (the corresponding LED will flash).
Pressing the On/Off button [1] inverts the operating status; the corresponding LED stops flashing
and the new status is displayed.
To exit service mode, press the SERVICE button [11] again. Otherwise this takes place
automatically 30 seconds after the last pressing of a button.
1 - Neutral sensor
The neutral sensor can inhibit UPS operation in the event that the neutral potential shifts
excessively from that of earth; during installation, it is used to verify the correct direction of the
power cable connection and to block operation in the event of error. To enable startup in this
case, invert the neutral and phase input cables and restart the UPS. The neutral anomaly is
signalled by modulated flashing of the red PROTECTION LED accompanied by the buzzer. This
function is normally enabled.
2 - Autorestart
This function enables the automatic restart of the UPS when the mains supply is restored after
UPS shutdown due to end of battery autonomy. Restart takes place in normal operation or in
the mode selected using the SERVICE button. This function is normally enabled.
→ neutral sensor is enabled
→ autorestart is enabled
→ Dip Speed is on
→ Extended PLL lock range is activated
→ load waiting mode is enabled
→ operation at 60 Hz
15