10. Technical data

Supply voltage
1 x 230-240 V –10%/+6%, 50 Hz, PE.
Motor protection
The pump requires no external motor protection.
Enclosure class
IP 42.
Insulation class
H.
Relative air humidity
Maximum 95%.
Ambient temperature
0°C to +40°C.
Temperature class
TF110 to CEN 335-2-51.
Liquid temperature
Maximum +110°C.
Continuously: +15°C to +95°C.
Pumps in domestic hot-water systems:
Continuously: +15°C to +60°C.
To avoid condensation in the terminal box and the
stator, the pumped liquid temperature must always
be higher than the ambient temperature. See the ta-
ble below:
Ambient
temperature
Min. [°C]
[°C]
15
20
25
30
35
40
System pressure
Pipe connection:
UPE 25-40, 25-40 A, 25-60, 25-60 A, 25-80,
32-40, 32-60 and 32-80: Maximum 10 bar.
Flange connection:
UPE 32-80 F, 40-80 F and 50-80 F: PN 6
(maximum 6 bar) or PN 10 (maximum 10 bar).
The system pressure is indicated on the pump
flanges.
Liquid temperature
Max. [°C]
15
110
20
110
25
110
30
110
35
90
40
70
Inlet pressure
The following minimum pressures must be available
at the pump inlet during operation:
Pump type
75°C
m head
UPE xx-40
0.5
UPE xx-60
0.5
UPE xx-80
0.5
EMC (electromagnetic compatibility)
EN 61 000-6-2.
EN 61 000-6-3.
Sound pressure level
The sound pressure level of the pump is lower than
43 dB(A).
Leakage current
The pump mains filter will cause a discharge current
to earth during operation. I
Inputs and outputs of expansion modules
External potential-free switch.
Start/stop input
Contact load: 5 V, 0.1 mA.
Screened cable.
Max. curve in-
Loop resistance:
put
Maximum 130 Ω/km.
Logical levels:
Logical zero: U < 1.5 V.
Min. curve input
Logical one: U > 4.0 V.
External signal: 0-10 VDC.
Input for analog
Maximum load: 0.1 mA.
0-10 V signal
Screened cable.
Internal potential-free change-
over contact.
Fault signal
Maximum load: 250 V, 2 A AC1.
module output
Minimum load: 5 V, 1 mA.
Screened cable.
Grundfos GENIbus protocol,
RS-485.
Bus input
Screened cable.
Lead cross section: 0.25 - 1 mm².
Cable length: Maximum 1200 m.
Liquid temperature
90°C
110°C
m head
m head
2.8
11.0
2.8
11.0
2.8
11.0
< 3.5 mA.
leakage
25